Warning: foreach() argument must be of type array|object, bool given in /var/www/html/web/app/themes/studypress-core-theme/template-parts/header/mobile-offcanvas.php on line 20

Consider two identical buildings: one in Los Angeles, California, where the atmospheric pressure is \(101 \mathrm{kPa}\) and the other in Denver, Colorado, where the atmospheric pressure is 83 kPa. Both buildings are maintained at \(21^{\circ} \mathrm{C}\), and the infiltration rate for both buildings is 1.2 air changes per hour (ACH). That is, the entire air in the building is replaced completely by the outdoor air 1.2 times per hour on a day when the outdoor temperature at both locations is \(10^{\circ} \mathrm{C}\). Disregarding latent heat, determine the ratio of the heat losses by infiltration at the two cities.

Short Answer

Expert verified
Question: Determine the ratio of heat losses by infiltration in two identical buildings at different atmospheric pressures in Los Angeles and Denver. Solution: 1. Calculate the air density at each location: - Los Angeles: \(ρ_{LA} = \frac{101 \times 10^3 \times 0.02897}{8.314\times 294.15}\) - Denver: \(ρ_{D} = \frac{83 \times 10^3 \times 0.02897}{8.314\times 294.15}\) 2. Calculate the mass flow rate of infiltration for each location: - Los Angeles: \(MFR_{LA} = 1.2 \times ρ_{LA}\) - Denver: \(MFR_{D} = 1.2 \times ρ_{D}\) 3. Determine the ratio of the heat losses by infiltration: - Ratio: \(Ratio = \frac{ρ_{LA}}{ρ_{D}}\) After calculating the air densities and mass flow rates for each location, use the formula for the ratio to find the answer.

Step by step solution

01

Air density calculation

First, we need to determine the air density at both locations. We can use the Ideal Gas Law equation and rearrange it to solve for density (ρ): $ ρ = \frac{PM}{RT} $ Where: - ρ is the air density - P is the pressure of the gas - M is the molar mass of the gas (28.97 g/mol for air) - R is the ideal gas constant (8.314 J/mol*K) - T is the temperature of the gas (in Kelvin) For Los Angeles, the atmospheric pressure is 101 kPa, and the temperature is 21°C, which is 294.15 K in Kelvin. $ ρ_{LA} = \frac{101 \times 10^3 \times 0.02897}{8.314\times 294.15} $ For Denver, atmospheric pressure is 83 kPa, and the temperature is 21°C, which is 294.15 K in Kelvin. $ ρ_{D} = \frac{83 \times 10^3 \times 0.02897}{8.314\times 294.15} $ Step 2: Calculate the mass flow rate of infiltration for each location
02

Mass flow rate calculation

Since we are given the infiltration rate in air changes per hour (ACH), we can simply multiply the infiltration rate (1.2 ACH) by the air density (ρ) to obtain the mass flow rate (MFR): $ MFR_{LA} = 1.2 \times ρ_{LA} $ $ MFR_{D} = 1.2 \times ρ_{D} $ Step 3: Determine the ratio of the heat losses by infiltration
03

Ratio of heat losses by infiltration

Now that we have the mass flow rate of infiltration for both locations, we can determine the ratio of the heat losses by infiltration at the two cities: $ Ratio = \frac{MFR_{LA}}{MFR_{D}} $ Plug in the MFR values calculated in Step 2: $ Ratio = \frac{1.2 \times ρ_{LA}}{1.2 \times ρ_{D}} $ Since the infiltration rate is the same for both locations, the 1.2 factor cancels out: $ Ratio = \frac{ρ_{LA}}{ρ_{D}} $ Now, we plug in the air densities calculated in Step 1 and solve for the ratio of the heat losses by infiltration.

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

Key Concepts

These are the key concepts you need to understand to accurately answer the question.

Air Density
When we talk about air density, we're referring to the mass of air per unit volume. It's crucial in various engineering and environmental calculations, including the analysis of heat loss due to infiltration in buildings.

Understanding air density helps in estimating the amount of heat required to maintain a certain indoor temperature. As demonstrated in the problem, the air density is different in Los Angeles and Denver due to the variation in atmospheric pressures. The ideal gas law is applied to calculate the air density because air can be treated as an ideal gas under typical atmospheric conditions.

Infiltration heat loss depends heavily on the density of the air that replaces indoor air, which is continuously changed due to infiltration. Lower density air, as seen at higher altitudes, will result in a different rate of heat loss compared to denser air at sea level. This is because denser air contains more molecules and thus, more capacity to carry heat.
Ideal Gas Law
The ideal gas law is fundamental in understanding the relationship between the pressure, volume, temperature, and the number of moles of a gas. For the purpose of calculations concerning air density, the ideal gas law equation is rearranged to solve for density with the formula \( ρ = \frac{PM}{RT} \).
  • \(P\) represents the pressure of air, which varies according to the location's altitude above sea level.
  • \(M\) is the molar mass of air, which is a constant.
  • \(R\) is the ideal gas constant.
  • \(T\) is the absolute temperature in Kelvin, highlighting the importance of converting Celsius to Kelvin in calculations.

In the exercise, the question requires that we use standard atmospheric conditions to calculate the density of air, which then informs our understanding of the heat loss by infiltration in the buildings located in Los Angeles and Denver.
Infiltration Rate
The infiltration rate quantifies the rate at which outdoor air enters a building, usually measured in air changes per hour (ACH). This rate is a critical factor in determining the heating and cooling loads for building design and energy efficiency assessments.

The infiltration rate provides us with an understanding of the volume of air exchanged and when multiplied by the density, it allows us to calculate the mass flow rate of air infiltrating a building. This mass flow rate directly affects the thermal load due to infiltration—the more significant the mass of air exchanged, the more heat is transported with it, leading to increased heat loss in winter or heat gain in summer.

The concept of infiltration rate is important in this exercise, as it shows that even with the same rate (1.2 ACH) for both cities, the heat loss varies depending on the air density, which is influenced by local atmospheric pressures as calculated using the ideal gas law.

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

Air at \(4.18 \mathrm{kg} / \mathrm{m}^{3}\) enters a nozzle that has an inletto-exit area ratio of 2: 1 with a velocity of \(120 \mathrm{m} / \mathrm{s}\) and leaves with a velocity of \(380 \mathrm{m} / \mathrm{s}\). Determine the density of air at the exit.

Determine the power input for a compressor that compresses helium from \(110 \mathrm{kPa}\) and \(20^{\circ} \mathrm{C}\) to \(400 \mathrm{kPa}\) and \(200^{\circ} \mathrm{C} .\) Helium enters this compressor through a \(0.1-\mathrm{m}^{2}\) pipe at a velocity of \(9 \mathrm{m} / \mathrm{s}\).

An insulated vertical piston-cylinder device initially contains \(0.11 \mathrm{m}^{3}\) of air at \(150 \mathrm{kPa}\) and \(22^{\circ} \mathrm{C}\). At this state, a linear spring touches the piston but exerts no force on it. The cylinder is connected by a valve to a line that supplies air at \(700 \mathrm{kPa}\) and \(22^{\circ} \mathrm{C}\). The valve is opened, and air from the high-pressure line is allowed to enter the cylinder. The valve is turned off when the pressure inside the cylinder reaches 600 kPa. If the enclosed volume inside the cylinder doubles during this process, determine ( \(a\) ) the mass of air that entered the cylinder, and \((b)\) the final temperature of the air inside the cylinder.

A vertical piston-cylinder device initially contains \(0.01 \mathrm{m}^{3}\) of steam at \(200^{\circ} \mathrm{C}\). The mass of the frictionless piston is such that it maintains a constant pressure of \(500 \mathrm{kPa}\) inside. Now steam at \(1 \mathrm{MPa}\) and \(350^{\circ} \mathrm{C}\) is allowed to enter the cylinder from a supply line until the volume inside doubles. Neglecting any heat transfer that may have taken place during the process, determine ( \(a\) ) the final temperature of the steam in the cylinder and \((b)\) the amount of mass that has entered.

A \(0.3-\mathrm{m}^{3}\) rigid tank is filled with saturated liquid water at \(200^{\circ} \mathrm{C}\). A valve at the bottom of the tank is opened, and liquid is withdrawn from the tank. Heat is transferred to the water such that the temperature in the tank remains constant. Determine the amount of heat that must be transferred by the time one-half of the total mass has been withdrawn.

See all solutions

Recommended explanations on Physics Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free