A smoking lounge is to accommodate 15 heavy smokers. The minimum fresh air requirement for smoking lounges is specified to be \(30 \mathrm{L} / \mathrm{s}\) per person (ASHRAE, Standard 62,1989 ). Determine the minimum required flow rate of fresh air that needs to be supplied to the lounge, and the diameter of the duct if the air velocity is not to exceed \(8 \mathrm{m} / \mathrm{s}\)

Short Answer

Expert verified
Answer: The minimum required flow rate of fresh air for 15 heavy smokers is 450 L/s and the diameter of the duct should be approximately 26.75 cm.

Step by step solution

01

Find the minimum required flow rate of fresh air

First, we need to calculate the total fresh air requirement for 15 heavy smokers. The fresh air requirement per person is 30 L/s. To find the total requirement, multiply this by the number of people: Total fresh air requirement = requirement per person × number of people Total fresh air requirement = 30 L/s × 15 Total fresh air requirement = 450 L/s
02

Convert the flow rate to cubic meters per second

To calculate the diameter of the duct, we need the flow rate in cubic meters per second (m³/s). To convert from liters per second (L/s) to cubic meters per second (m³/s), divide the flow rate by 1000: Flow rate (m³/s) = Total fresh air requirement / 1000 Flow rate (m³/s) = 450 L/s / 1000 Flow rate (m³/s) = 0.45 m³/s
03

Calculate the cross-sectional area of the duct

Now, we will use the flow rate and the maximum air velocity (8 m/s) to calculate the cross-sectional area (A) of the duct. Use the formula: Area (m²) = Flow rate (m³/s) / Air velocity (m/s) Area (m²) = 0.45 m³/s / 8 m/s Area (m²) ≈ 0.05625 m²
04

Calculate the diameter of the duct

Since the duct is circular, we can use the formula for the area of a circle to find its diameter. The formula for the area of a circle is: Area (m²) = π × (diameter/2)² Now, we will solve for the diameter: Diameter = 2 × √(Area / π) Plugging in the calculated area: Diameter = 2 × √(0.05625 m² / π) Diameter ≈ 0.2675 m
05

Convert the diameter to its appropriate unit

The diameter is calculated in meters. To convert it into a more commonly used unit, like centimeters, multiply the diameter by 100: Diameter (cm) = Diameter (m) × 100 Diameter (cm) = 0.2675 m × 100 Diameter (cm) ≈ 26.75 cm So, the minimum required flow rate of fresh air that needs to be supplied to the lounge is 450 L/s, and the diameter of the duct should be approximately 26.75 cm for the air velocity not to exceed 8 m/s.

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

Determine the power input for a compressor that compresses helium from \(110 \mathrm{kPa}\) and \(20^{\circ} \mathrm{C}\) to \(400 \mathrm{kPa}\) and \(200^{\circ} \mathrm{C} .\) Helium enters this compressor through a \(0.1-\mathrm{m}^{2}\) pipe at a velocity of \(9 \mathrm{m} / \mathrm{s}\).

Submarines change their depth by adding or removing air from rigid ballast tanks, thereby displacing seawater in the tanks. Consider a submarine that has a \(700 \mathrm{m}^{3}\) air-ballast tank originally partially filled with \(100 \mathrm{m}^{3}\) of air at \(1500 \mathrm{kPa}\) and \(15^{\circ} \mathrm{C}\). For the submarine to surface, air at \(1500 \mathrm{kPa}\) and \(20^{\circ} \mathrm{C}\) is pumped into the ballast tank, until it is entirely filled with air. The tank is filled so quickly that the process is adiabatic and the seawater leaves the tank at \(15^{\circ} \mathrm{C}\). Determine the final temperature and mass of the air in the ballast tank.

A sealed electronic box is to be cooled by tap water flowing through the channels on two of its sides. It is specified that the temperature rise of the water not exceed \(4^{\circ} \mathrm{C}\) The power dissipation of the box is \(2 \mathrm{kW}\), which is removed entirely by water. If the box operates 24 hours a day, 365 days a year, determine the mass flow rate of water flowing through the box and the amount of cooling water used per year.

The air in an insulated, rigid compressed-air tank whose volume is \(0.5 \mathrm{m}^{3}\) is initially at \(4000 \mathrm{kPa}\) and \(20^{\circ} \mathrm{C}\) Enough air is now released from the tank to reduce the pressure to 2000 kPa. Following this release, what is the temperature of the remaining air in the tank?

An air compressor compresses 15 L \(/\) s of air at 120 kPa and \(20^{\circ} \mathrm{C}\) to \(800 \mathrm{kPa}\) and \(300^{\circ} \mathrm{C}\) while consuming \(6.2 \mathrm{kW}\) of power. How much of this power is being used to increase the pressure of the air versus the power needed to move the fluid through the compressor?

See all solutions

Recommended explanations on Physics Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free