Consider is a zero sequence fault current, is positive sequence fault
current and is negative sequence fault current.
Consider is zero sequence fault voltages, is positive sequence fault voltage and is negative sequence fault voltage.
Consider is line to ground voltage at phase, is line to ground voltage at phase b and is line to ground voltage at phase
.
Assumeis fault voltage regarding a bolted three phase fault.
Determine the sequence component of line to ground voltages at the fault terminals.
..............1
![]()
Here,and are Thévenin equivalent reactance and , and are sequence fault currents.
Determine bolted three phase fault, the sequence fault currents are
![]()
And ![]()
From equation (1), the sequence fault voltages are
=
=0
![]()
Since, lines to ground voltage are

![]()
Therefore, for a bolted three phase to ground fault sequence fault currents and are zero sequence fault voltages are zero and line to ground voltages are zero.
.