Chapter 9: Q55P (page 586)
A single-line diagram of a four-bus system is shown in Figure 9.27. Equipment ratings and per-unit reactances are given as follows.
Machine and:
Transformers and:
On a base of 100 MVA and 345 kV in the zone of the transmission line, the series reactances of the transmission line areand . (a) Draw each of the sequence networks and determine the bus impedance matrix for each of them. (b) Assume the system to be operating at nominal system voltage without prefault currents when a bolted line-to-line fault occurs at bus 3. Compute the fault current, the line-to-line voltages at the faulted bus, and the line-to-line voltages at the terminals of machine 2. (c) Assume the system to be operating at nominal system voltage without prefault currents, when a bolted double line-to ground fault occurs at the terminals of machine 2. Compute the fault current and the line-to-line voltages at the faulted bus.
Short Answer
(a)
Draw the zero-sequence network of the system.
Draw the positive-sequence network of the system.
Draw the negative-sequence network of the system.
(b)
The value of zero sequence bus impedance matrix is .
The value of positive sequence bus impedance matrix is .
The value of negative sequence bus impedance matrix is
(b)
The value of positive, negative and zero sequence component of the bolted line-to-line fault occurs at bus-3 , and is , and 0 pu.
The value of line to line voltages at the faulted bus , and are 1.732 pu, 0.886 pu and 0.866 pu.
The value of line to line voltages , and at the terminals of the machine are 1.732 pu, 4.26 pu and -0.798 pu.
(c)
The value of sub-transient fault currents at the faulted bus is .
The value of line to line voltages, , and at the faulted bus are 1.704 pu, 0 pu and 0 pu.