Warning: foreach() argument must be of type array|object, bool given in /var/www/html/web/app/themes/studypress-core-theme/template-parts/header/mobile-offcanvas.php on line 20

Using the bus impedance matrices determined in Problem 9.51, verify the fault currents for the faults given in Problems 9.10, 9.24, 9.25, 9.26, and 9.27.

Short Answer

Expert verified

(a)

The value of sub-transient fault current in the systemI'a is j0.609 pu.

(b)

The value of sub-transient fault current in the systemI'a is j0.483 pu.

(c)

The value of sub-transient fault current in the systemI'a is j0.483 pu.

(d)

The value of sub-transient fault current in phases of a systemI''aI''bI''c is 02.113180°2.1130° p.u.

(e)

The value of sub-transient fault current in phases of a systemI''aI''bI''c is0.125900.642157.5°0.64222.48° p.u.

Step by step solution

01

Write the given data from the question.

As reference Problem 9.13

The fault impedance in per unit is ZF=j0.1 perunit.

Thevalue of base MVA is 100 MVA.

The value of voltage in the zone of generator G2 is 15 kV.

02

Determine the formula of line-to-line fault and line-to-ground fault.

Write the formula of sub-transient fault current in the system.

I''a=I1 …… (1)

Here,I1 are phase sequence currents.

Write the formula of sub-transient fault current in the system.

I''a=3Ι0 …… (2)

Here,Ι0 are phase sequence currents.

Write the formula of sub-transient fault current in the system.

I''a=3Ι0 …… (2)

Here,Ι0 are phase sequence currents.

Write the formula of sub-transient fault current in the system.

I''aI''bI''c=1111a2a1aa2I0I1I2 …… (3)

Here I0,I1 androle="math" localid="1656425516200" I'2 are phase sequence currents.

03

(a) Determine the sub-transient fault current in the system.

Determine the per-unit positive sequence reactance for generator 1.

X1=X''d=0.21210210050=0.576 p.u.

Determine the per-unit negative sequence for generator 1.

X2=0.576 p.u.

Determine the per-unit zero sequence reactance for generator 1.

X0=0.11210210050=0.288 p.u.

Determine the per-unit positive sequence reactance for generator 2.

X1=X''d=0.2 p.u.

Determine the per-unit negative sequence for generator 2.

X2=0.23 p.u.

T2 Determine the per-unit zero sequence reactance for generator 2.

X0=0.1 p.u.

Determine the per unit reactance for transformer T1.

XT1=0.1010050=0.2 p.u.

Determine the per unit reactance for transformer T2.

XT2=0.10 p.u.

Determine the base impedance value.

Zbase=138×10321000×106=190.44Ω

Determine the per unit positive and negative quantities for lines.

X1=X2=40190.44=0.210 p.u.

Determine the per unit zero sequence reactance for line.

X0=100190.44=0.5251 p.u.

Draw the positive-sequence network of the system.

For a system with positive-sequence impedance, write the expression for the bus impedance matrix.

Zbus=1Ybus=Ybus1

Determine theYbusmatrix.

Ybus=j0.7760.20000.20.410.210000.210.420.210000.210.310.10000.10.3 p.u.

Determine the bus impedance matrix for positive-sequence impedance.

Zbus=j0.7760.20000.20.410.210000.210.420.210000.210.310.10000.10.31=j1.63971.3621.09750.83310.27771.3625.28464.25843.23231.07741.09754.25847.26885.51731.83910.83313.23235.51737.80232.60080.27771.07741.83912.60084.2003 p.u.

Draw a circuit diagram of per-unit negative sequence network.

Determine the Ybus.

Ybus=j0.7760.20000.20.410.210000.210.420.210000.210.310.10000.10.33 p.u.

Determine the bus impedance matrix for positive-sequence impedance.

Zbus=j0.7760.20000.20.410.210000.210.420.210000.210.310.10000.10.331=j1.63761.3541.08390.81380.24661.3545.25364.20563.15760.95691.08394.20567.17875.38991.63330.81383.15765.38997.62212.30970.24660.95691.63332.30973.7302 p.u.

Determine the diagram for zero-sequence impedance.

Determine theYbusmatrix.

Ybus=j0.4880.20000.20.72510.52510000.52511.05020.62610000.52510.6261000000.1 p.u.

Determine the bus impedance matrix for positive-sequence impedance.

Zbus=j0.4880.20000.20.72510.52510000.52511.05020.52510000.52510.6261000000.1=j2.92872.1461.84791.549802.1465.23634.5093.781601.84794.5095.52254.631601.54983.78164.63165.48170000010 p.u.

Determine the positive-sequence impedance of Ybus.

Ybus=Z11=1.6397 p.u.

Determine the negative-sequence impedance of Ybus.

Ybus=Z11=1.6376

Determine the zero-sequence impedance of Ybus.

Ybus=Z11=2.9287

When a 3-phase fault occurs in a system:

Determine the fault current in a positive-sequence component.

I1=EgZ1=1j1.6397=j0.609 pu

Since the fault is symmetrical, the zero and negative sequence currents are zero.

I0=I2=0

Determine the sub-transient fault current in the system.

Substitutej0.609 puforI1into equation (1).

I''a=I1=j0.609 pu

Therefore, the value of sub-transient fault current in the systemI'ais j0.609 pu.

04

(b) Determine the sub-transient fault current in the system.

When a single line-to-ground fault occurs in a system:

Positive, negative, and zero sequence fault currents are all the same for a single line to ground fault.

Determine the fault current in the sequence components.

I0=EgZ0+Z1+Z2=1j2.9287+1.6397+1.6376=1j6.206=j0.161 pu

Determine the sub-transient fault current in the system.

Substitutej0.161 forI0 into equation (2).

I''a=3I0=3j0.161=j0.483 pu

05

(c) Determine the sub-transient fault current in the system.

When a single line-to-ground fault through fault impedance occurs in a system:

Positive, negative, and zero sequence fault currents are all the same for a single line to ground fault.

Determine the fault current in the sequence components.

I0=EgZ0+Z1+Z2+3ZF=1j2.9287+1.6397+1.6376+30.05=1j6.356=j0.157 pu

Determine the sub-transient fault current in the system.

Substitutej0.157 forI0 into equation (2).

I''a=3I0=3j0.157=j0.472 pu

06

(d) Determine the sub-transient fault current in the system.

When a line-to-line fault occurs in a system.

For line-line line fault.

I1=I2I0=0

Determine the fault current in a positive-sequence component:

I1=EgjZ1+Z2=1j1.6397+1.6376=1j3.2773=j0.305 pu

Determine the fault current in a positive-sequence component.

I2=I1=j0.305 p.u.

Determine the fault current in a zero-sequence component.

I0=0

Determine the sub-transient fault current in phases of a system.

Substitute 0 for I0,j0.305 pu for I1andj0.305 pu forI2 into equation (3).

I''aI''bI''c=1111a2a1aa20j0.305 puj0.305 pu=02.113180°2.1130° p.u.

Therefore, the value of sub-transient fault currentI''aI''bI''c in phases of a system is 02.113180°2.1130° p.u.

07

(e) Determine the sub-transient fault current in phases of a system.

When bolted double line-to-ground fault occurs in a system:

Determine the fault current in a positive-sequence component.

I1=EgjX1+X2X0+3X0=1j1.6397+1.63760.731.6376+0.73=1j2.144=j0.466 pu

Determine the fault current in a negative-sequence component.

I2=Z0Z0+Z1+3Z0I1=2.92872.9287+1.6397+1.6376j0.466=0.4719j0.466=j0.219 pu

Determine the fault current in a sequence component.

I0=Z2Z0+Z1+3Z2I1=1.63762.9287+1.6397+1.6376j0.466=0.2638j0.466=j0.122 pu

Determine the sub –transient fault currents in phases of a system.

I''aI''bI''c=1111a2a1aa2j0.122j0.466j0.219=j0.122j0.466+j0.219j0.122j0.466a2+j0.219aj0.122j0.466a+j0.219a2=0.1256900.642157.5°0.64222.48° pu

Therefore, the value of sub-transient fault currentI''aI''bI''c in phases of a system is 0.125900.642157.5°0.64222.48° p.u.

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

For power-system fault studies, it is assumed that the system is operating under balanced steady-state conditions prior to the fault, and sequence networks are uncoupled before the fault occurs.

(a) True (b) False

A 500 MVA, 13.8 kV synchronous generator withXd"=X2=0.20and X0=0.05per unit is connected to a500MVA,13.8kV/500kVY transformer with 0.10 per-unit leakage reactance. The generator and transformer neutrals are solidly grounded. The generator is operated at no-load and rated voltage, and the high-voltage side of the transformer is disconnected from the power system. Compare the sub transient fault currents for the following bolted faults at the transformer high-voltage terminals: three-phase fault, single line-to-ground fault, line-to-line fault, and double line-to-ground fault.

For the five-bus network shown in Figure 9.25, a bolted single-line-toground fault occurs at the bus2 end of the transmission line between buses 1and. role="math" localid="1656410079694" 2The fault causes the circuit breaker at the bus end of the line to open, but all other breakers remain closed. The fault is shown in Figure 9.26. Compute the subtransient fault current with the circuit breaker at the bus- 2end of the faulted line open. Neglect prefault current and assume a prefault voltage ofrole="math" localid="1656410247948" 1.0 per unit.

Faults at bus n in Problem 9.8 are of interest (the instructor selects , or ). Determine the Thevenin equivalent of each sequence network as viewed from the fault bus. Prefault voltage is 1.0 per unit. Prefault load currents and D–Y phase shifts are neglected.

Compute the 4×4per-unit zero-, positive-, and negative-sequence bus impedance matrices for the power system given in Problem 9.5. Use a base of and 20kVin the zone of generatorG3.

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free