Warning: foreach() argument must be of type array|object, bool given in /var/www/html/web/app/themes/studypress-core-theme/template-parts/header/mobile-offcanvas.php on line 20

Using the bus impedance matrices determined in Problem 9.47, verify the fault currents for the faults given in Problems 9.4(b), 9.4(c), and 9.19 (a through d).

Short Answer

Expert verified

(a)The value of fault current in the phase sequence componentI0,data-custom-editor="chemistry" I1andI2is0,j7.89 p.uand 0.

(b) The value of subtransient fault current of single-line-to ground fault isj9.146 p.u .

(c) The value of subtransient fault current of single-line-to ground fault isj9.146 p.u .

(d) The value of subtransient fault current of a single line-to-ground fault through fault impedance,j5.87 p.u.

(e) The value of subtransient fault current of a bolted line-to-line faultI''a,I''bandI''cis0, 6.84180° p.u,6.840° p.u.

(f) The value of subtransient fault current of bolted double line-to-ground faultj10.86 p.u,.

Step by step solution

01

Write the given data from the question.

As reference of problem 9.47.

Refer to the Figure 9.17 from the textbook.

Assume the following data for a single-line diagram of a three-phase power system.

The value of base MVA is1000 MVA.

The value of voltage base for generator side is15 kV.

The neutral reactance is 0.05 per unit.

Assume that the arc impedance,ZF=15+j0Ω .

The base impedance of the network, Zbase=250Ω.

02

Determine the formula of sequence impedance bus matrix and subtransient fault current.

Write the formula of fault current in the positive-sequence component.

I1=EgZ11-1 …… (1)

Here,role="math" localid="1656483053732" Egis generated voltage andZ111is line to line impedance.

Write the formula of subtransient fault current in the system.

role="math" localid="1656483175386" I''a=3I0 …… (2)

Here, role="math" localid="1656483229073" I0is zero sequence component.

Write the formula of subtransient fault current in the phase of the system.

I''a=0 …… (3)

Here,I''ais phase of the system

Write the formula of subtransient fault current in the phase of the system.

I''b=j3I1 …… (4)

HereI1, is positive sequence component.

Write the formula of subtransient fault current in the phase of the system.

I''c=I''b …… (5)

Here,I''bis subtransient fault current in the phase of the system

03

(a)Determine thefault current in the phase sequence component.

As reference of problem 9.4 (b).

Determine the base impedance of transmission line.

Zbase=500×10321000×106=250Ω

Determine the per unit quantities for lines.

Determine the per unit zero quantity for line 1-2.

X12=150Ω250Ω=0.6 p.u.

Determine the per unit zero quantities for line 1-3 and 2-3.

X13=X23=100Ω250Ω=0.4 p.u

Determine the per unit positive and negative quantities for line 1-2.

X12=50Ω250Ω=0.2 p.u.

Determine the per unit positive and negative quantities for line 1-3 and 2-3.

X13=X23=40Ω250Ω=0.16 p.u.

The circuit's zero-sequence bus admittance matrix is shown below.

Ybus0=j14.1671.672.51.6714.1672.52.52.513.34

Determine the bus impedance, Zbus0using the following expression.

Zbus0=1Ybus0

Here,Ybus0is zero-sequence bus admittance matrix.

Substitute14.1671.672.51.6714.1672.52.52.513.34forYbus0into above equation.

Zbus0=114.1671.672.51.6714.1672.52.52.513.34=j0.07480.01170.01620.01170.07480.01620.01620.01620.081

Therefore, the value of zero-sequence bus impedance matrix is,

Zbus0=j0.07480.01170.01620.01170.07480.01620.01620.01620.081

Draw the circuit diagram of per unit positive-sequence single line diagram.

The circuit's positive-sequence bus admittance matrix is shown below.

Ybus1=j14.821456.25514.58346.256.256.2516.2037

Determine the bus impedance,Zbus1using the following expression.

Zbus1=1Ybus1

Here, Ybus1is positive-sequence admittance matrix.

Substitute14.821456.25514.58346.256.256.2516.2037forYbus1into above equation.

Zbus1=114.821456.25514.58346.256.256.2516.2037=j0.12660.07710.07860.07710.12910.07950.07860.07950.1227

Therefore, the value of positive-sequence bus impedance matrix is,

Zbus1=j0.12660.07710.07860.07710.12910.07950.07860.07950.1227

Draw the circuit diagram of per unit negative-sequence single line diagram.

The circuit's negative-sequence bus admittance matrix is shown below.

Ybus2=j14.821456.25514.58346.256.256.2516.2037

Determine the bus impedance, Zbus2using the following expression.

Zbus2=1Ybus2

Here, Ybus2is negative-sequence bus admittance matrix.

Substitute14.821456.25514.58346.256.256.2516.2037forYbus2into above equation.

Zbus2=114.821456.25514.58346.256.256.2516.2037=j0.12660.07710.07860.07710.12910.07950.07860.07950.1227

Therefore, the value of negative-sequence bus impedance matrix is,

Zbus2=j0.12660.07710.07860.07710.12910.07950.07860.07950.1227

Assume that a 3-phase fault occurs in the system with a pre-fault voltage of.1.0perunit

Determine the fault current in the positive-sequence component.

Substitute1forEgandj0.1266forZ111into equation (1).

I1=1 Vj0.1266=j7.89 p.u

Determine the fault currents in the negative-and zero-sequence component are zero.

I0=I2=0

04

(b) Determine the subtransient fault current of single-line-to ground fault.

As reference of problem 9.4 (c).

Assume that a single line-to ground fault occurs in the system with a pre-fault voltage of1.0perunit

Determine the fault current in the sequence components.

I0=I1=I2=EgZ111+Z111+Z112=1j0.0748+0.1266+0.1266=j3.0487 p.u

Determine the subtransient fault current in the system.

Substitutej3.0487forI0into equation (2).

I''a=3j3.0487=j9.146 p.u

05

(c) Determine the subtransient fault current of single-line-to ground fault.

As reference of problem 9.19 (a).

Assume that a single line-to ground fault occurs in the system with a pre-fault voltage of1.0perunit.

Determine the fault current in the sequence components.

I0=I1=I2=EgZ111+Z111+Z112=1j0.0748+0.1266+0.1266=j3.0487 p.u

Determine the subtransient fault current in the system.

Substitutej3.0487forI0into equation (2).

B=3-j3.0487=-j9-1460.u

06

(d) Determine the subtransient fault current of a single line-to-ground fault through fault impedance.

As reference of problem 9.19 (b).

Consider that a system with a pre fault voltage of1.0perunitexperiences a single line-to-ground fault through fault impedance.

Determine the per unit fault impedance of the system.

ZFpu=ZFZbase=15Ω250Ω=0.06 p.u

Determine the fault current in the sequence components.

I0=I1=I2=EgZ110+Z111+Z112+3ZFpu=1j0.0748+0.1266+0.1266+30.06=j1.956 p.u

Determine the subtransient fault current in the system.

Substitutej1.956forI0into equation (3).

I''a=3j1.956=j5.87 p.u

07

(e) Determine the subtransient fault current of a bolted line-to-line fault.

As reference of problem 9.19 (c).

Assume that the system experiences a bolted line-to-line fault with a pre-fault voltage of1.0perunit.

Determine the fault current in the positive-sequence component.

I1=I2=EgjZ111+Z112=1j0.1266+0.1266=j3.95 p.u

The fault current in the zero-sequence component,I0=0.

Determine the subtransient fault currents in the phases of the system.

I''a=0

Determine the subtransient fault currents in the phases of the system.

Substitutej3.95forI1into equation (4).

I''b=j3j3.95=6.84180° p.u

Determine the subtransient fault currents in the phases of the system.

I''c=6.840° p.u

08

(f) Determine the subtransient fault current of bolted double line-to-ground fault.

As reference of problem 9.19 (d).

Determine the bolted double line-to-ground fault occurs in the system.

Determine the fault current in the positive-sequence component

I1=EgjX1+X2 parallel with X0=1 Vj0.1266+0.12660.07480.1266+0.0748=1 Vj0.1736=j5.76 p.u

Determine the fault current in the zero-sequence component.

I0=I1Z112Z110+Z111=j5.76j0.1266j0.1266+j0.0748=j5.760.6285=j3.62 p.u

Determine the subtransient fault current.

Substitute j3.62for I0into equation (2).

I''a=3j3.62=j10.86 p.u

Therefore, the value of subtransient fault current are computed and verify is j10.86 p.u.

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

For a bolted three-phase-to-ground fault, sequence-fault currents ________ are zero, sequence fault voltages are ______, and line-to-ground voltages are ________.

Equipment ratings for the four-bus power system shown in Figure 7.14 are given as follows:

GeneratorG1:500MVA,13.8kV,X''d=X2=0.20,X0=0.10perunit

GeneratorG2:750MVA,18kV,X''d=X2=0.18,X0=0.09perunit

GeneratorG3:1000MVA,20kV,X''d=0.17,X2=0.20,X0=0.09perunit

TransformerT1:500MVA,13.8D/500kVY,X=0.12perunit

TransformerT2:750MVA,18/500kVY,X=0.10perunit

TransformerT3:1000MVA,20/500kVY,X=0.10perunit

Each line: X1=50ohms,X0=150ohms

The inductor connected to generator neutral has a reactance of . Draw the zero, positive, and negative-sequence reactance diagrams using a base in the zone of generator. Neglect transformer phase shifts.

Equipment ratings for the five-bus power system shown in Figure 7.15 are given as follows:

GeneratorG1:50MVA,12kV,X''d=X2=0.20,X0=0.10perunit

GeneratorG2:100MVA,15kV,X''d=0.2,X2=0.23,X0=0.10perunit

TransformerT1:50MVA,10kVY/138kVY,X=0.10perunit

TransformerT2:100MVA,15/138kVY,X=0.10perunit

Each line: X1=40ohms,X0=100ohms

Draw the zero-, positive-, and negative-sequence reactance diagrams using a 100 MVA,15 KV , base in the zone of generator G2. NeglectΔ-Y transformer phase shifts.

Consider the one line diagram of a simple power system shown in Figure 9.20. System data in per-unit on a 100MVAbase are given as follows:

Synchronous generators:

G1              100MVA              20kV               X1=X2=0.15                  X0=0.05G2              100MVA             20kV              X1=X2=0.15                  X0=0.05

Transformers:

T1                     100MVA            20/220kV            X1=X2=X0=0.1aT2                     100MVA            20/220kV            X1=X2=X0=0.1

Transmission lines:

L12               100MVA         220kV      X1=X2=0.125                X0=0.3L13               100MVA         220kV      X1=X2=0.15                X0=0.35L23               100MVA         220kV      X1=X2=0.25                X0=0.7125

The neutral of each generator is grounded through a current-limiting reactor of æ 0.08333 per unit on a100MVA base. All transformer neutrals are solidly grounded. The generators are operating no-load at their rated voltages and rated frequency with their EMFs in phase. Determine the fault current for a balanced three-phase fault at bus 3 through a fault impedance ZF=0.1per unit on a100MVA base. Neglect Δ-Yphase shifts.

Consider the system shown in Figure 9.18. (a) As viewed from the fault at F, determine the Thevenin equivalent of each sequence network. Neglect phase shifts. (b) Compute the fault currents for a balanced three phase fault at fault point F through three fault impedances ZFA=ZFB=ZFC=j0.5per unit. Equipment data in per-unit on the same base are given as follows:

Synchronous generators:

G1X1=0.2X2=0.12X0=0.06G2X1=0.33X2=0.22X0=0.066

Transformers:

T1X1=X2=X0=0.2T2X1=X2=X0=0.225T3X1=X2=X0=0.27T4X1=X2=X0=0.16

Transmission lines:

L1X1=X2=0.14X0=0.3L1X1=X2=0.35X0=0.6

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free