Chapter 9: Q46P (page 585)
Repeat Problem 9.43 for a bolted double line-to-ground fault at bus 1.
Short Answer
The fault current and voltages are and respectively.
Chapter 9: Q46P (page 585)
Repeat Problem 9.43 for a bolted double line-to-ground fault at bus 1.
The fault current and voltages are and respectively.
All the tools & learning materials you need for study success - in one app.
Get started for free(a) Repeat Problem 9.14 for the case of Problem 9.4 (b).
(b) Repeat Problem 9.19(a) for a single line-to-ground arcing fault with arc impedance ZF 5 (15 1 j0) V.
(c) Repeat Problem 9.19(a) for a bolted line-to-line fault.
(d) Repeat Problem 9.19(a) for a bolted double line-to-ground fault.
(e) Repeat Problems 9.4(a) and 9.19(a) including D–Y transformer phase shifts. Assume American standard phase shift. Also calculate the sequence components and phase components of the contribution to the fault current from generator n (n 5 1, 2, or 3) as specified by the instructor in Problem 9.4(b).
The venin equivalent sequence networks looking into the faulted bus of a power system are given with , , and per unit. Compute the fault currents and voltages for the following faults occurring at the faulted bus:
(a) Balanced three-phase fault
(b) Single line-to-ground fault
(c) Line-line fault
(d) Double line-to-ground fault. Which is the worst fault from the viewpoint of the fault current?
Faults at bus n in Problem 9.8 are of interest (the instructor selects , or ). Determine the Thevenin equivalent of each sequence network as viewed from the fault bus. Prefault voltage is 1.0 per unit. Prefault load currents and D–Y phase shifts are neglected.
Compute the per-units zero-, positive-, and negative-sequence bus impedance matrices for the power system given in Problem 9.8. Use a base of and in the zone of generator.
Repeat Problem 9.38 for a bolted single line-to-ground fault at bus 1.
What do you think about this solution?
We value your feedback to improve our textbook solutions.