Warning: foreach() argument must be of type array|object, bool given in /var/www/html/web/app/themes/studypress-core-theme/template-parts/header/mobile-offcanvas.php on line 20

(a) Compute the 3 x 3 per-unit zero-, positive-, and negative-sequence bus impedance matrices for the power system given in Problem 9.1. Use a base of 1000 MVA and 765 kV in the zone of line 1-2.

(b) Using the bus impedance matrices determined in Problem 9.42, verify the fault currents for the faults given in Problems 9.3, 9.14, 9.15, 9.16, and 9.17.

Short Answer

Expert verified

(a)

The value of 3 x 3 per unit zero-sequence bus impedance matrix, Zbus0for the system is j0.06140.01920.02370.01920.06140.02370.02370.02370.0639.

The value of 3 x 3 per unit positive-sequence bus impedance matrix,Zbus1for the system is j0.0950.07140.06880.07140.09590.06920.06880.06920.0852.

The value of 3 x 3 per unit negative-sequence bus impedance matrix,Zbus2for the system is j0.09730.07380.07170.07380.09830.07220.07170.07220.0888.

(b)

The value of sub-transient fault current in the system I0is 0.

The value of sub-transient fault current in the systemI''ais j11.825 p.u.

The value of sub-transient fault current in the systemI''aisj7.431 p.u.

The value of sub-transient fault current in the phases of the system I''aI''bI''c=0990° p.u.

The value of sub-transient fault current in the systemI0is j13.73 p.u.

Step by step solution

01

Write the given data from the question.

As reference Problem 9.1

Thevalue of base MVA is 1000 MVA.

The value of fault impedanceZFis 30+j0Ω.

The value of base impedance of the networkZbaseis 585.225Ω.

The value of voltage in the zone of line 1-2 is 765 kV.

02

Determine the formula of 3 x 3 per-unit zero-, positive-, and negative-sequence bus impedance matrices for the power system and sub-transient fault current in the system.

Write the formula of per unit-zero sequence bus impedance matrix.

Zbus0=1Ybus0 …… (1)

Here,Ybus0 is zero-sequence bus admittance matrix.

Write the formula of per unit-positive sequence bus impedance matrix.

Zbus1=1Ybus1 …… (2)

Here,Ybus1 is positive-sequence bus admittance matrix.

Write the formula of per unit-negative sequence bus impedance matrix.

Zbus2=1Ybus2 …… (3)

Here,Ybus2 is negative-sequence bus admittance matrix.

Write the formula of sub-transient fault current in the system.

I0=I2 …… (4)

Here,I2 are phase sequence currents.

Write the formula of sub-transient fault current in the system.

I''a=3Ι0 …… (5)

Here,Ι0 are phase sequence currents.

Write the formula of sub-transient fault current in the system.

I''aI''bI''c=1111a2a1aa2I0I1I2 …… (6)

Here, I0,I1 andI'2 are phase sequence currents.

03

(a) Determine the sub-transient fault current in the system.

See the textbook's figure 9.17, which is a single-line diagram of a three-phase power system.

Determine the base impedance of transmission line.

Zbase=765×10321000×106=585225×1061000×106=585.225Ω

Determine the per unit quantities for lines.

Determine the per unit zero quantity for line 1-2.

X12=150Ω585.225Ω=0.256 p.u.

Determine the per unit zero quantities for lines 1-3 and 2-3.

X13=X23=100Ω585.225Ω=0.17 p.u

Determine the per unit positive and negative quantities for line 1-2.

X12=50585.225Ω=0.085 p.u.

Determine the per unit positive and negative quantities for lines 1-3 and 2-3.

X13=X23=40Ω585.225Ω=0.068 p.u.

Draw a circuit diagram of per unit zero-sequence single line diagrams.

Determine the zero-sequence bus admittance matrix for the circuit.

Ybus0=j19.783.906255.883.9062519.785.885.885.8820

Now, determine the bus impedance matrix, Zbus0.

Substitute 19.783.906255.883.9062519.785.885.885.8820for Ybus0into equation (1).

Zbus0=1j19.783.906255.883.9062519.785.885.885.8820=j0.06140.01920.02370.01920.06140.02370.02370.02370.0639

Therefore,the value of 3 x 3 per unit zero-sequence bus impedance matrix,Zbus0for the system is j0.06140.01920.02370.01920.06140.02370.02370.02370.0639.

Draw a circuit diagram of per-unit positive sequence single line diagram.

Determine the positive-sequence bus admittance matrix for the circuit.

Ybus1=j30.04211.764714.705811.764729.803914.705814.705814.705835.5544

Now, determine the bus impedance matrix, Zbus1.

Substitute 30.04211.764714.705811.764729.803914.705814.705814.705835.5544for Ybus1into equation (2).

Zbus1=1j30.04211.764714.705811.764729.803914.705814.705814.705835.5544=j0.0950.07140.06880.07140.09590.06920.06880.06920.0852

Therefore, the value of 3 x 3 per unit zero-sequence bus impedance matrix, Zbus1for the system is j0.0950.07140.06880.07140.09590.06920.06880.06920.0852

Determine the positive-sequence bus admittance matrix for the circuit.

Ybus2=j30.04211.764714.705811.764729.803914.705814.705814.705835.5544

Now, determine the bus impedance matrix,Zbus2.

Substitute 30.04211.764714.705811.764729.803914.705814.705814.705835.5544forYbus2into equation (3).

Zbus2=1j30.04211.764714.705811.764729.803914.705814.705814.705835.5544=j0.09730.07380.07170.07380.09830.07220.07170.07220.0888

Therefore, the value of 3 x 3 per unit zero-sequence bus impedance matrix,Zbus2for the system isj0.09730.07380.07170.07380.09830.07220.07170.07220.0888.

04

(b) Determine the sub-transient fault current in the system.

Assume that the system experiences a 3-phase fault with a prefault voltage of 1.0 per unit.

Determine the fault current in the positive sequence components.

I1=ERZ111=1 Vj0.095Ω=j10.53 p.u

Determine the sub-transient fault current in the system.

Substitute 0 forI0into equation (4).

I0=0

Assume that the system experiences a single line-to-ground fault with a prefault voltage of 1.0 per unit.

Determine the fault current in the sequence components.

I0=I1=I2=EgZ110+Z111+Z112=1 Vj0.0614+0.095+0.0973

Solve further as,

role="math" localid="1656414216442" I0=j3.942 p.u

Determine the sub-transient fault current in the system.

Substitutej3.942forI0into equation (5).

I''a=3j3.942=j11.825 p.u

Consider a system with a pre-fault voltage of 1.0 per unit that experiences a single line-to-ground fault through fault impedance.

Determine the per unit fault impedance of the system.

ZFPu=ZFZbase=30Ω585.225Ω=0.05 p.u

Determine the fault current in the sequence components.

I0=I1=I2=EgZ110+Z111+Z112+3ZFpu=1j0.0614+0.095+0.0973+30.05

Solve further as,

I0=j2.477 p.u

Determine the sub transient fault current in the system.

Substitutej2.477forI0into equation (5).

I''a=3j2.477=j7.431 p.u

Consider a system with a pre-fault voltage of 1.0 per unit that experiences a bolted line-to-line fault through fault impedance.

Determine the fault current in the positive-sequence component.

I1=I2=EgZ111+Z112=1j0.095+0.0973=j5.2 p.u

The fault current in the zero-sequence component, I0=0.

Determine the sub transient fault currents in the phases of the system.

Substitute 0 for I''a, -9pu forI''b and90° p.u forI''c into equation (6).

I''aI''bI''c=1111a2a1aa20j5.2 p.uj5.2 p.u°

Assume that a bolted double line-to-ground fault occurs in the system.

Determine the fault current in a positive-sequence component.

I1=EgX1+X2 parallel with X0=1​ Vj0.095+0.09730.06140.0973+0.0614=1​ Vj0.1326=j7.5389 p.u

Determine the fault current in the zero-sequence component.

I0=I1Z112Z110+Z111=j7.5389j0.095j0.0614+j0.095=j7.53890.607=j4.579 p.u

Determine the sub-transient fault current.

Substitutej4.579 forI0 into equation (5).

I''a=j13.73 p.u

Therefore, the bus impedance matrices are obtained, the fault current are determine and verified.

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

Repeat Problem 9.38 for a bolted line-to-line fault at bus 1.

Question: Equipment ratings for the four-bus power system shown in Figure 7.14 are given as follows:

Generator

Generator

Generator

Transformer

Transformer

Transformer

Each line:

The inductor connected to generator neutral has a reactance of . Draw the zero, positive, and negative-sequence reactance diagrams using a base in the zone of generator. Neglect transformer phase shifts.

A 500 MVA, 13.8 kV synchronous generator withXd"=X2=0.20and X0=0.05per unit is connected to a500MVA,13.8kV/500kVY transformer with 0.10 per-unit leakage reactance. The generator and transformer neutrals are solidly grounded. The generator is operated at no-load and rated voltage, and the high-voltage side of the transformer is disconnected from the power system. Compare the sub transient fault currents for the following bolted faults at the transformer high-voltage terminals: three-phase fault, single line-to-ground fault, line-to-line fault, and double line-to-ground fault.

Faults at bus n in Problem 9.1 are of interest (the instructor selects n=1,2or3). Determine the Thevenin equivalent of each sequence network as viewed from the fault bus. Pre fault voltage is 1.0 per unit. Pre fault load currents and Δ-Ytransformer phase shifts are neglected. (Hint: Use the Y-Δconversion in Figure 2.33.)

For the five-bus network shown in Figure 9.25, a bolted single-line-toground fault occurs at the bus2 end of the transmission line between buses 1and. role="math" localid="1656410079694" 2The fault causes the circuit breaker at the bus end of the line to open, but all other breakers remain closed. The fault is shown in Figure 9.26. Compute the subtransient fault current with the circuit breaker at the bus- 2end of the faulted line open. Neglect prefault current and assume a prefault voltage ofrole="math" localid="1656410247948" 1.0 per unit.

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free