Warning: foreach() argument must be of type array|object, bool given in /var/www/html/web/app/themes/studypress-core-theme/template-parts/header/mobile-offcanvas.php on line 20

Repeat Problem 9.38 for a bolted double line-to-ground fault at bus 1.

Short Answer

Expert verified

The fault current and voltages08.605147°8.60533° pu are and0.7500.4733217.6°0.4733142.4° pu respectively.

Step by step solution

01

Write the given data from the question.

The pre fault voltage for each bus in the positive sequence network,VF=10° pu

Write the zero-sequence impedance matrix,

Zbus0=j0.100000.200000.10perunit

Write the positive and negative-sequence impedance matrix,

role="math" localid="1656159400122" Zbus1=Zbus2Zbus1=j0.120.080.040.080.120.060.040.060.08perunit

02

Determine the equations to calculate the per-unit fault current and per-unit voltage at bus 2 for a bolted line to line fault at bus 1.

The equation to calculate the positive sequence fault current is given as follows.

I1-1=VFZ11-1+Z11-2||Z11-0 …… (1)

The equation to calculate the negative sequence fault current is given as follows.

I1-2=-I1-1(Z11-0Z11-0+Z11-2) …… (2)

The equation to calculate the zero-sequence fault current is given as follows.

I1-0=-I1-1(Z11-2Z11-0+Z11-2) …… (3)

The equation to calculate the voltage at bus 2 (from 9.5.9 of textbook equation) is given as follows.

[V2-0V2-1V2-2]=[0VF0]-[Z2-0000Z2-1000Z2-2][I2-0I2-1I2-2] …… (4)

The equation to calculate the fault voltage is given as,

[V2agV2bgV2cg]=[1111a2a1aa2][V2-0V2-1V2-3] …… (5)

The equation to calculate the fault current is given as,

[I1aI1bI1c]=[1111a2a1aa2][I1-0I1-1I1-2] …… (6)

03

Calculate the per-unit fault current and per-unit voltage at bus 2 for a bolted line to line fault at bus 1.

Calculate the positive sequence component of fault current.

Substitute 10° pufor VF, j0.12 pufor Z111, j0.12 pufor Z112, and j0.10 puforZ110into equation (1).

I11=10°j0.12+j0.12j0.10I11=10°j0.1745I11=j5.729 pu

Calculate the negative sequence component of fault current.

Substitutej5.729 pufor I11,j0.12 pufor Z112, andj0.10 puforZ110into equation (2).

I2=j5.729 pu×j0.10j0.10+j0.12I2=j5.729×j0.10j0.22I2=j2.604 pu

Calculate the zero-sequence component of fault current.

Substitutej5.729 pufor I11,j0.12 pufor Z112and j0.10 puforZ0into equation (3).

I0=j5.729 pu×j0.12j0.1+j0.12I0=j5.729 pu×j0.12j0.22I0=j3.125 pu

Calculate the voltages at bus 2.

Substitute j3.125 pufor I10, j5.729 pufor I11,j2.604 pufor I12,0 pufor Z20, j0.08 pufor Z21andj0.08 pufor Z22into equation (4).

V2-0V2-1V2-2=010°00000j0.08000j0.08j3.125 puj5.729 puj2.604 puV2-0V2-1V2-2=010°000.45830.2083V2-0V2-1V2-2=00.54170.2083 pu

Calculate the fault voltage.

Substitute00.54170.2083 puforV2-0V2-1V2-2 into equation (5).

V2agV2bgV2cg=1111a2a1aa200.54170.2083V2agV2bgV2cg=0.7500.4733217.6°0.4733142.4° pu

Calculate the fault current.

Substitute j3.125 pufor I10, j5.729 pufor I11,j2.604 pu for I12, into equation (6).

I1aI1bI1c=1111a2a1aa2j3.125 puj5.729 puj2.604 puI1aI1bI1c=08.605147°8.60533° pu

Therefore, the fault current and voltages are 08.605147°8.60533° puand 0.7500.4733217.6°0.4733142.4° purespectively.

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

A single-line diagram of a four-bus system is shown in Figure 9.27. Equipment ratings and per-unit reactances are given as follows.

Machine and: 100MVAX0=0.04 20kVXn=0.05 X1=X2=0.2

Transformers and: 100MVAX1=X2=X0=0.08 20Δ/345YkV

On a base of 100 MVA and 345 kV in the zone of the transmission line, the series reactances of the transmission line areX1=X2=0.15and X0=0.5perunit. (a) Draw each of the sequence networks and determine the bus impedance matrix for each of them. (b) Assume the system to be operating at nominal system voltage without prefault currents when a bolted line-to-line fault occurs at bus 3. Compute the fault current, the line-to-line voltages at the faulted bus, and the line-to-line voltages at the terminals of machine 2. (c) Assume the system to be operating at nominal system voltage without prefault currents, when a bolted double line-to ground fault occurs at the terminals of machine 2. Compute the fault current and the line-to-line voltages at the faulted bus.

The single-line diagram of a three-phase power system is shown in Figure 9.17. Equipment ratings are given as follows:

Synchronous generators:

G1         1000MVA            15kV            X''d=X2=0.18,X0=0.07perunit  G2        1000MVA            15kV             X''d=X2=0.20,X0=0.10perunit  G3         500MVA            13.8kV           X''d=X2=0.1507,X0=0.05perunitG4         750MVA            13.8kV           X''d=0.30,X2=0.40,X0=0.10perunit   

Transformers:

T1         1000MVA            15kVΔ/765kVY           X0=0.10perunitT2        1000MVA            15kVΔ/765kVY            X0=0.10perunit  T3         500MVA             15kVΔ/765kVY           X0=0.12perunitT4         750MVA             15kVΔ/765kVY           X0=0.111perunit

Transmission line:

1-2       765kV                X1=50Ω,  X0=150Ω1-3         765kV                X1=40Ω,  X0=100Ω2-3         765kV                X1=40Ω,  X0=100Ω

The inductor connected to Generator 3 neutral has a reactance of0.05perunit using generator 3 ratings as a base. Draw the zero-, positive-, and negative-sequence reactance diagrams using a1000MVA,765kV base in the zone of line 1–2. Neglect theΔ-Y transformer phase shifts.

Compute the 3 x 3 per-unit zero-, positive-, and negative-sequence bus impedance matrices for the power system given in Problem 4(a). Use a base of 1000 MVA and 500 kV in the zone of line 1-2.

For a double line-to-ground fault through a fault impedance ZF, the sequence networks are to be connected ________, at the fault terminal; additionally, ________ is to be included in series with the zero-sequence network.

In order of frequency of occurrence of short-circuit faults in three-phase power systems, list those: ________, ________, ________, ________.

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free