Draw the sequence network of the given system as,

Calculate the equivalent impedance of the zero-sequence network.
![]()
Calculate the equivalent impedance of the positive-sequence network.
![]()
Calculate the equivalent impedance of the negative-sequence network.
![]()
Calculate the base current.
Substitute for and for into equation (1).
![]()
The zero and negative sequence current for three phase faults are zero.
![]()
Calculate the positive sequence current for thee phase fault.
Substitute for and for into equation (2).
![]()
Calculate the sub transient current for three phase faults.
Substitute for into equation (3).
![]()
Calculate the sub transient current for three phase faults in kA.
Substitute for and for into equation (4).
![]()
Calculate the fault current is sequence component for line to ground faults.
Substitute for , for , for and for into equation (5).
![]()
Calculate the sub-transient fault current in per unit for line to ground faults.
Substitute for into equation (6).
![]()
Calculate the sub-transient fault current in kA.
Substitute for and for into equation (7).
![]()
The zero-sequence current for line to line fault is zero.
![]()
Calculate the positive and negative sequence fault current for line to line faults.
Substitute for , for and for into equation (8).
![]()
Calculate the sub transient current for line to line faults.
Substitute for into equation (9).
![]()
Calculate the sub-transient fault current in kA.
Substitute forand for into equation (10).
![]()
Calculate the positive sequence component of fault current for double line to line faults.
Substitute for , for , for and for into equation (11).
![]()
Calculate the negative sequence component of fault current for double line to line faults.
Substitute for , for andfor into equation (12).
![]()
Calculate the zero-sequence component of fault current for double line to line faults.
Substitute for , for andfor into equation (13).
![]()
Calculate the sub transient current for double line to line faults.
Substitute for , for and forinto equation (14).
Calculate the sub-transient fault current in kA.
Substitute forand for into equation (15).
![]()
Hence, the sub transient fault current for three phase fault, line to ground fault, single line to line fault and double line to line fault are,,and respectively.