Since the fault is three phase fault therefore only positive sequence network is existing.
Draw the positive sequence network of the line diagram.

Convert the delta into star as,
The impedance between the line 1 and neutral of the star connection.
The impedance between the line 2 and neutral of the star connection.
The impedance between the line 3 and neutral of the star connection.
The required diagram is shown in Figure below.

Reduce the positive sequence network as,
The Thevenin equivalent of positive sequence network is shown below.

The no load generated EMF is and fault impedance is .
The Thevenin equivalent of positive sequence network with fault impedance.

The positive sequence current from the above circuit.
Calculate the base current as.
Substitute for , and for into equation (1)
Calculate the fault current.
Substitute for and for into equation (2).
Hence, the fault current for three phase faults is .