Warning: foreach() argument must be of type array|object, bool given in /var/www/html/web/app/themes/studypress-core-theme/template-parts/header/mobile-offcanvas.php on line 20

Question: Determine the subtransient fault current in per-unit and in kA during a bolted three-phase fault at the fault bus selected in Problem 9.9.

Short Answer

Expert verified

Answer

The sub transient fault current in per unit and kA are 2.823-90°2.823150°2.82330°puand 16.30-90°16.30150°16.3030°kArespectively.

Step by step solution

01

Write the given data from the question:

Write the rating of the generators.

The power rating of generatorG1 is 50 MVA, the voltage rating is 15 KV, the reactance and are Xd''equal X2 to and the value of X0 is 0.10 unit.

The power rating of generatorG2 is 100 MVA , the voltage rating is 12 KV, the reactance is ,is and Xd''equal X2 to and the value of X0is 0.10 unit. .

The power rating of transformer T1is 100 MVA, the voltage rating is 10KV Y/138 KV Y, and the value X0is 0.10 per unit. .

The power rating of transformer T2is 50 MVA, the voltage rating is 15KV Y/138 KV Y, and the value X0is 0.10 per unit. .

The reactance of each line,X1 is 40Ω andX0 is 100Ω.

The base MVA, Sbase=100 MVA

The base voltage for generator side, Vbase=15 KV

The prefault fault voltage,VF = 1 per unit

02

Determine the formulas to calculate the reactance of the zero, positive and negative sequence network.

The equation to calculate the reactance on the new base value is given as follows.

Xpunew=XpuoldKVbaseoldKVbasenewMVAbasenewMVAbaseold …… (1)

Here (Xpu)new is the per unit value on new base values, (Xpu)old is the per unit value on old base values,(KVbase)old it the old voltage rating,(KVbase)new is the new voltage rating,(MVAbase)old is the new power rating and (MVAbase)new is the old power rating.

The equation to calculate the base impedance is given as follows.

Zbase=KV2MVA …… (2)

Here, Zbase is the base value, is the power rating, is the voltage rating.

The equation to calculate the new per unit impedance of the transmission line is given as follows.

I1=VFZ1 …… (3)

The equation to calculate current in the positive sequence circuit is given as follows.

Xnew=XoldZbase …… (4)

Here is the positive sequence impedance and is the fault voltage.

The equation to calculate the base current is given as follows.

Ibase=Sbase3Vbase …… (5)

The equation to calculate sub transient current is given as follows.

[I''aI''bI''c]=[1111a2a1aa2][I0I1I2] …… (6)

Here and are the sub transient current, and are the sequence current.

The equation to calculate per quantities is given as follows.

Ipu=IbaseI'' …… (7)

Here is the sub transient current.

03

 Step 3: Calculate the reactance of the zero, positive and negative sequence network.

Calculate the new value of the reactance of generator 1.

For positive and negative sequence reactance.

Substitute 50 MVA for (MVAbase)old , 12 KV for(KVbase)old , 0.20pu for (X1)odd, 100 MVA for (MVAbase)new , 10 KV for(KVbase)new into equation (1).

X1new=X2newX1new=X''dnewX1new=0.20×122102×10050X1new=0.576pu

For zero-sequence reactance.

Substitute 50 MVA for (MVAbase)old , 12 KV for(KVbase)old , 0.10pu for (X1)odd, 100 MVA for (MVAbase)new , 10 KV for(KVbase)new into equation (1).

X0new=0.10×122102×10050X0new=0.288pu

As the base old MVA and KV values of generator 2 is same as the new value, therefore the reactance of generator remains the same.

X1=X''dX1=0.2puX2=0.23puX0=0.1pu

Calculate the new value of the reactance of transformer 1.

Substitute 50 MVA for (MVAbase)old , 12 KV for(KVbase)old , 0.10pu for (X1)odd, 100 MVA for (MVAbase)new , 10 KV for(KVbase)new into equation (1).

XT1new=0.10×102102×10050XT1new=0.20pu

Calculate the new value of the reactance of transformer 2.

Substitute 50 MVA for (MVAbase)old , 12 KV for(KVbase)old , 0.10pu for (X1)odd, 100 MVA for (MVAbase)new , 10 KV for(KVbase)new into equation (1).

XT2new=0.10×102102×100100XT2new=0.10pu

Calculate the base impedance.

Substitute 1000 MVA for Sbase and 138 KV for Vbase into equation (2).

Zbase=13821000Zbase=190.44Ω

Calculate the positive and negative sequence reactance for line.

Substitute 190.44 for Zbase and 40 for Xold into equation (3)

X1=X2X1=40190.44X1=0.210pu

Calculate the zero-sequence reactance for line.

Substitute 190.44 for Zbase and 40 for Xold into equation (3)

X0=100190.44X0=0.5251pu

Draw the positive sequence network.

Calculate the positive-sequence equivalent impedance.

Calculate current in the positive sequence circuit.

Substitute j=0.3542 for Z1 and 1.0< 00 for VFinto equation (4).

X1=0.5760.2+0.21+0.1+0.2X1=0.5760.92\X1=0.3542pu\

Calculate the base current.

Substitute 100 MVA for Sbase and 10 KV for Vbase into equation (5)

localid="1656421248875" Ibase=1003×10Ibase=5.774kA

Since the fault is symmetrical, therefore, zero and negative sequence currents are zero.

I0=I2I0=0A

Calculate the sub transient fault current in per unit.

Substitute 0.A for I0 ,I 2 ,and -j 2.823 for I1 into equation (6).

localid="1656422035328" I''aI''bI''c=1111a2a1aa20-j2.8230I''aI''bI''c=0-j2.82300-j2.823a200-j2.823a+1I''aI''bI''c=2.823-90°2.823150°2.82330°pu

Calculate the sub transient current in kA.

Substitute 2.823-90°2.823150°2.82330°pufor Id '' and 5.774 k for Ibase into equation (7).

I''aI''bI''c=2.823-90°2.823150°2.82330°×5.774I''aI''bI''c=16.30-90°16.30150°16.3030°KA

Hence the sub transient fault current in per unit and kA are width="121">2.823-90°2.823150°2.82330°and 16.30-90°16.30150°16.3030°respectively.

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

Question: Faults at bus n in Problem 9.5 are of interest (the instructor selects or ). Determine the Thevenin equivalent of each sequence network as viewed from the fault bus. Prefault voltage is per unit. Prefault load currents and phase shifts are neglected.

Consider the one line diagram of a simple power system shown in Figure 9.20. System data in per-unit on a 100MVAbase are given as follows:

Synchronous generators:

G1              100MVA              20kV               X1=X2=0.15                  X0=0.05G2              100MVA             20kV              X1=X2=0.15                  X0=0.05

Transformers:

T1                     100MVA            20/220kV            X1=X2=X0=0.1aT2                     100MVA            20/220kV            X1=X2=X0=0.1

Transmission lines:

L12               100MVA         220kV      X1=X2=0.125                X0=0.3L13               100MVA         220kV      X1=X2=0.15                X0=0.35L23               100MVA         220kV      X1=X2=0.25                X0=0.7125

The neutral of each generator is grounded through a current-limiting reactor of æ 0.08333 per unit on a100MVA base. All transformer neutrals are solidly grounded. The generators are operating no-load at their rated voltages and rated frequency with their EMFs in phase. Determine the fault current for a balanced three-phase fault at bus 3 through a fault impedance ZF=0.1per unit on a100MVA base. Neglect Δ-Yphase shifts.

A 500 MVA, 13.8 kV synchronous generator withXd"=X2=0.20and X0=0.05per unit is connected to a500MVA,13.8kV/500kVY transformer with 0.10 per-unit leakage reactance. The generator and transformer neutrals are solidly grounded. The generator is operated at no-load and rated voltage, and the high-voltage side of the transformer is disconnected from the power system. Compare the sub transient fault currents for the following bolted faults at the transformer high-voltage terminals: three-phase fault, single line-to-ground fault, line-to-line fault, and double line-to-ground fault.

The single-line diagram of a three-phase power system is shown in Figure 9.17. Equipment ratings are given as follows:

Synchronous generators:

G1         1000MVA            15kV            X''d=X2=0.18,X0=0.07perunit  G2        1000MVA            15kV             X''d=X2=0.20,X0=0.10perunit  G3         500MVA            13.8kV           X''d=X2=0.1507,X0=0.05perunitG4         750MVA            13.8kV           X''d=0.30,X2=0.40,X0=0.10perunit   

Transformers:

T1         1000MVA            15kVΔ/765kVY           X0=0.10perunitT2        1000MVA            15kVΔ/765kVY            X0=0.10perunit  T3         500MVA             15kVΔ/765kVY           X0=0.12perunitT4         750MVA             15kVΔ/765kVY           X0=0.111perunit

Transmission line:

1-2       765kV                X1=50Ω,  X0=150Ω1-3         765kV                X1=40Ω,  X0=100Ω2-3         765kV                X1=40Ω,  X0=100Ω

The inductor connected to Generator 3 neutral has a reactance of0.05perunit using generator 3 ratings as a base. Draw the zero-, positive-, and negative-sequence reactance diagrams using a1000MVA,765kV base in the zone of line 1–2. Neglect theΔ-Y transformer phase shifts.

Using the bus impedance matrices determined in Problem 9.51, verify the fault currents for the faults given in Problems 9.10, 9.24, 9.25, 9.26, and 9.27.

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free