Warning: foreach() argument must be of type array|object, bool given in /var/www/html/web/app/themes/studypress-core-theme/template-parts/header/mobile-offcanvas.php on line 20

Repeat Problem 9.24 for a bolted line-to-line fault.

Short Answer

Expert verified

The value of sub transient fault current is02.4318002.4300perunit and 014.03180014.0300kA.

The value of contributions to the fault current from each generator isj0.00921.502-179.801.502-0.20perunit and 3.463-9001.73189.401.73190.60kA.

The value of contributions to the fault current from each transformer is-j0.0110.925179.6600.9250.340perunit and 4.932-9001.731-90.601.731-89.40kA.

Step by step solution

01

Write the given data from the question.

The circuit zero sequence impedance is Z0.

The positive sequence impedance of the circuit is Z1.

The negative sequence impedance of the circuit is Z2.

I0Is the zero sequence current flowing through zero sequence impedance Z0.

I1Is the positive sequence current flowing through positive impedance Z1.

I2Is the negative sequence current flowing through negative sequence impedance Z2.

Ia,Ib andIc are phase currents.

VFIs the pre-fault bus voltage in the positive-sequence network.

02

Determine the formula of per unit reactance of generator, motor and neutral reactor.

Write the formula of sub transient fault current.

[IaIbIc]=[1111a2a1aa2][I0I1I2] …… (1)

Here,I0 is a zero sequence current,I1 is the current flowing through impedanceZ1 andI2 is the current flowing through impedance Z2.

Write the formula ofcontributions to the fault current from each generator.

[IG1-aIG2-bIG3-c]=[1111a2a1aa2][IG1-0IG1-1IG1-2] …… (2)

Here, IG1-0is the fault current by zero sequence generator G1, role="math" localid="1656392539847" IG1-1is fault current by positive sequence generator role="math" localid="1656392563995" G1and role="math" localid="1656392579832" IG1-2is fault current by negative sequence generator G1.

Write the formula ofcontributions to the fault current from each transformer.

IT1-aIT1-bIT1-c=1111a2a1aa2IT1-1IT1-1IT1-2 …… (3)

Here, IT1-0is the fault current by zero sequence transform, IT1-1is the fault current by positive sequence transformer T1, IT1-2is the fault current by negative sequence transformer T1.

03

 Determine the sub transient fault current, contributions to the fault current from each generator and contributions to the fault current from each transformer.

Refer to figure 7.15 in the textbook of five bus power system.

Determine the per-unit positive sequence reactances for generator 1.

X1=Xd*=0.21210210050=0.576p.u.

Determine the per-unit negative sequence reactances for generator 1.

X2=0.576p.u.

Determine the per-unit zero sequence reactances for generator 1.

X0=0.11210210050=0.288p.u.

Determine the per-unit positive sequence reactances for generator.

X1=Xd*=0.2p.u.

Determine the per-unit negative sequence reactances for generator.

X2=0.23p.u.

Determine the per-unit zero sequence reactances for generator.

X0=0.1

Determine the per-unit positive sequence reactances for transformer.

localid="1656394643848" XT1=0.1010050=0.2p.u.

XT2=0.10p.u.

Determine the base impedance value.

Zbase=1.38×1032100×106=190.44Ω

Determine the per unit positive sequence line reactance equal to negative sequence line reactances.

X1=X2=40190.44=0.210p.u.

Determine the zero sequence reactance is.

X0=100190.44=0.5251p.u.

Draw the per unit zero-sequence network.

Figure 1

Draw the per unit positive sequence network.

Figure 2

Draw the per unit negative sequence network.

Figure 3

Now assume bus 1 is faulty bus.

Calculate the zero sequence equivalent impedance from figure 1.

Z0=j0.2+j0.5251+j0.5251+j0.1=j1.3502p.u.

Draw zero sequence Thévenin equivalent circuit is shown in figure.

Figure 4

Draw the Thévenin equivalent circuit for zero sequence is shown in figur


Figure 5

Now assume bus 1 is faulty bus.

Calculate the negative sequence equivalent impedance from figure 3.

Z2=j0.576Pj0.2+j0.21+j0.21+j0.1+0.23=j0.576Pj0.95=j0.576j0.95j0.576+j0.95=j0.3586p.u.

Draw the Thévenin equivalent circuit for negative sequence is shown in figure 5


Figure 6

Draw the Thévenin equivalent circuit for negative sequence is shown in figure

Figure 7

Calculate the positive sequence equivalent impedance from figure 2.

Z1=j0.576Pj0.2+j0.21+j0.21+j0.1+0.2=j0.576Pj0.92=j0.576j0.92j0.576+j0.92=j0.3542p.u.

Draw the Thévenin equivalent circuit for positive sequence for bus is shown in figure.

Figure 8

Draw the Thévenin equivalent circuit for positive sequence is shown in figure.

Figure 9

Draw the bolted line-to-line fault values of impedance bus and is shown in figure 10.

Figure 10

Determine the sequence current through each impedance.

I1=-I2=VFZ1+Z2=100j0.3542+j0.3586=-j1.1403p.u.

Determine the sub transient fault current.

Substitute 0for I0, -j1.403for I1and j1.403for I2into equation (1).

IaIbIc=1111a2a1aa20-j1.403j1.403=02.43180024300perunit

Change in kA.

localid="1656396808984" IaIbIc=02.4318002.4300100103kA=014.03180014.0300kA

Therefore, the sub transient fault current 02.4318002.4300perunitand 014.03180014.0300kA.

Determine the contribution of fault current by zero sequence for generatorG1is IG1-0=0

Determine the contribution of fault current by zero sequence for transformer T1is IT1-0=0perunit.

Draw the circuit diagram of positive sequence network.


Figure 11

Determine the currents from GeneratorG1as.

IG1-1=-j1.4030.920.92+.576=-j1.4030.615=-j0.8628perunit

Determine the currents from Transformer T1as.

IT1-1=-j1.403.5760.92+.576=-j0.54perunit

Draw the circuit diagram of negative sequence network.

Figure 12

Determine the current of Generator G1.

IG1-2=-j1.4030.950.95+.76=j1.4030.622=j0.872perunit

Determine the current of Transformer T1.

IT1-2=-j0.4847.576.576+0.95=j1.4030.377=j0.529perunit

Determine the contribution to the fault current from each generator.

Substitute 0for IG1-0, -j0.8628for IG1-1and j0.872for IG1-2into equation (2).

IG1-aIG1-bIG1-c=1111a2a1aa20-j0.8628j0.872=j0.00921.502-179.801.502-0.20perunit

Change in kA.

IG1-aIG1-bIG1-c=j0.00921.502-179.801.502-0.20100103kA=0.0539008.67-179.808.67-0.20kA

Therefore, the value of contributions to the fault current from each generator is 3.463-9001.73189.401.73190.60kA.

Determine the contribution to the fault current from each transformer.

Substitute 0for IT1-0, -j0.54for IT1-1and j0.529for IT1-2into equation (3).

IT1-aIT1-bIT1-c=1111a2a1aa20-j0.54j0.529=-j0.0110.925179.6600.9250.340perunit

Change in kA.

IT1-aIT1-bIT1-c=-j0.0110.925179.6600.9250.340100103kA=0.063-9005.34179.6605.340.340kA.

Therefore, the value of contributions to the fault current from each transformer is 0.063-9005.34179.6605.340.340kA.

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

(a) Compute the 3 x 3 per-unit zero-, positive-, and negative-sequence bus impedance matrices for the power system given in Problem 9.1. Use a base of 1000 MVA and 765 kV in the zone of line 1-2.

(b) Using the bus impedance matrices determined in Problem 9.42, verify the fault currents for the faults given in Problems 9.3, 9.14, 9.15, 9.16, and 9.17.

Question:For the system of Problem 9.11, compute the fault current and voltages at the fault for the following faults at point F: (a) a bolted single line-to-ground fault; (b) a line-to-line fault through a fault impedance ZF =j0.05; (c) a double line-to-ground fault from phase B to C to ground, where phase B has a fault impedance ZF =j0.05 , phase C also has a fault impedance ZF =j0.05, and the common line-to-ground fault impedance is ZG =j0.033 per unit.

As shown in Figure 9.21 (a), two three-phase buses abcand a'b'c'are interconnected by short circuits between phases band b' and between c and c', with an open circuit between phases a and a' . The fault conditions in the phase domain are Ia=Ia'=0 and Vbb'=Vcc'=0. Determine the fault conditions in the sequence domain and verify the interconnection of the sequence networks as shown in Figure 9.15 for this one conductor-open fault.

For a double line-to-ground fault through a fault impedance ZF, the sequence networks are to be connected ________, at the fault terminal; additionally, ________ is to be included in series with the zero-sequence network.

Determine the sub transient fault current in per-unit and in kA, as well as the per-unit line-to-ground voltages at the fault bus for a bolted single line-to-ground fault at the fault bus selected in Problem 9.2.

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free