Determine the maximum voltage available on the high voltage side of the transformer.
Therefore, the value of the maximum voltage available on the high voltage side of the transformer is 205.17 kV.
Refer to Table 13.2 station class surge arrestor in the text book.
The maximum rms L - G voltage is given in kVin the second column of table 13.2 from the textbook.
Therefore, choose a station-class surge arrestor with a 209 kV maximum continuous over-voltage (MCOV) value and an AZES metal oxide surge arrestor with a 258 kVMCOV value.
From table 13.2 in the text book, the fifth column states the FOW protective level.
The safe margin of discharge voltage for the chosen surge arrestor is (2.19 - 2.36) per unit of MCOV for an 10 kV impulse current cresting in 0.5 ms.
Determine the minimum value of the protective margin.
Therefore, the minimum value of the protective margin is, 806.76 kV.
Determine the maximum value of the protective margin.
Therefore, the maximum value of the protective margin is 1306.76 kV.
Therefore, the range of the protective margin is (506.76 kV - 1306.76 kV).
Determine the protective margin ranges:
to which is greater than 1.4, as required.
Therefore, the value of protective margin ranges from (3.86 pu - 6.25 pu)of MCOV.