(a)
Determine the real power.
Substitute for for localid="1655292065913" for in equation (1).
Determine the full load current at receiving end.
Substitute 1914 MW for in equation (2).
Determine the receiving end voltage.
Substitute role="math" localid="1655353311115" for A ,role="math" localid="1655353351026" for B , for and role="math" localid="1655353525402" for in equation (3).
role="math" localid="1655353766213"
From solving above equation,
Here,
Therefore, voltage drop limit not satisfied.
Determine the receiving end current.
Substitute for A , for B , for and for , for in equation (3).
From solving above equation,
Determine the power.
Substitute 0.99 for pf , 1.84 kA for , for in equation (4).
Therefore, the practical loadability is 1499 MW .