Connect the 33 kV CTs in the delta on the star side and the CTs in the star on the delta side (11kV).
Determine the transformer primary rated line current as:
Choose a 500:5 standard CT ratio on the primary side. The following is the CT secondary current :
Here, is transformer primary rated line current.
Substitute 524.88 for and for into above equation.
Determine the transformer secondary rated line current is calculated similarly as follows:
Choose a 2000:5 standard CT ratio on the secondary side. The following is the CT secondary current :
Here, is transformer secondary rated line current.
Substitute 1574.64 for and for into above equation.
Due to CT's delta position on the secondary side. As a result, the current in the restraint winding is:
Determine the relay current for differentially protected transformer.
Substitute 6.82 for Is and 5.25 for Ip into equation (1).
Therefore, the value of relay current Ir is 1.57 .
Determine the overload ratio is given as. So, the relay setting should be:
Substitute 1.57 for Ir into equation (2).
Therefore, the minimum relay setting is 3.14 A .