Warning: foreach() argument must be of type array|object, bool given in /var/www/html/web/app/themes/studypress-core-theme/template-parts/header/mobile-offcanvas.php on line 20

Question:Consider a three-phase Δ--Y connected, 30-MVA,33:11KV , transformer with differential relay protection. If the CT ratios are 500:5A on the primary side and 2000:5A on the secondary side, compute the relay current setting for faults drawing up to 200% of rated transformer current.

Short Answer

Expert verified

Answer

The value of relay current I at differential protected is 1.57 A and the minimum relay setting is 3.14 A.

Step by step solution

01

Write the given data from the question.

Consider the value of transformer power rating is 15 MVA .

Consider the value of transformer primary voltage is 33 KV .

Consider the value of transformer secondary voltage is 11 KV.

Consider percentage overload is 200% .

02

Determine the formula of relay current   and relay setting  for faults drawing up to 200%.

Write the formula ofrelay current.

i=ris-iP …… (1)

Here, Is is CT secondary current.

Write the formula of minimum relay setting.

I'r=Ir×200% …… (2)

Here, Ir is relay current.

03

 Determine the value of relay current   and relay setting  for faults drawing up to 200%.

Connect the 33 kV CTs in the delta on the star side and the CTs in the star on the delta side (11kV).

Determine the transformer primary rated line current I1rated as:

I1rated=30×10633×103×3=524.88A

Choose a 500:5 standard CT ratio on the primary side. The following is the CT secondary currentiP :

iP=I1ratedCTratio

Here, is transformer primary rated line current.

Substitute 524.88 for I1rated and 5005for into above equation.

iP=524.885005=5.25A

Determine the transformer secondary rated line current is calculated similarly as follows:

I2rated=30×10611×103×3=1574.64A

Choose a 2000:5 standard CT ratio on the secondary side. The following is the CT secondary current :

IS=I2ratedCTratio

Here, is transformer secondary rated line current.

Substitute 1574.64 for I2rated and 20005for into above equation.

IS=1574.6420005=3.92A

Due to CT's delta position on the secondary side. As a result, the current in the restraint winding is:

iS=IS×3=3.92×3=6.82A

Determine the relay current for differentially protected transformer.

Substitute 6.82 for Is and 5.25 for Ip into equation (1).

Ir=6.82-5.25=1.57A

Therefore, the value of relay current Ir is 1.57 .

Determine the overload ratio is given as. So, the relay setting should be:

Substitute 1.57 for Ir into equation (2).

I'r=1.57×2A=3.14A

Therefore, the minimum relay setting is 3.14 A .

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

Consider the transmission line shown in Figure 10.48 with series impedanceZL, negligible shunt admittance, and load impedance ZRat the receiving end. (a) Determine ZRfor the given conditions of VR=1.0perunitandSR=2+j0.8perunit. (b) Construct the impedance diagram in the R-X plane for ZL=0.1+j0.3. (c) FindZSfor this condition and the angle δbetween ZSandZR.

Figure 10.48

Given the open-delta VT connection shown in Figure 10.38, both VTs having a voltage rating of 240 kV : 120 V, the voltages are specified as VAB=2300,VBC=230-120andVBC=230120. Determine Vab, Vbc and Vca for the following cases: (a) The dots are shown in Figure 10.38. (b) The dot near c is moved to b in Figure 10.38.

Question:Determine the CT ratios for differential protection of a three-phase,Δ--Y connected,10-MVA,33:11 KV , transformer, such that the circulating current in the transformer D does not exceed 5A .

A CT with an excitation curve given in Figure 10.39 has a rated current ratio of500:5Aand a secondary leakage impedance of 1+j0.5. Calculate the CT secondary output current and the CT error for the following cases: (a) The impedance of the terminating device is 9+j0.5and the primary CT load current is 400A. (b) The impedance of the terminating device is 9+j0.5and the primary CT fault current is 1200A. (c) The impedance of the terminating device is 4.9+j1.5and the primary CT load current is 400A. (d) The impedance of the terminating device is role="math" localid="1655725625321" 4.9+j1.5and the primary CT fault current is1200A



.

In addition to the costs of the relays, what other costs should be considered when upgrading relays?

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free