Choose the CT ratio first.
Determine the transformer primary rated current.
Substitute for and for into equation (1).
Therefore, the value of transformer primary rated current , is .
Choose a 300:5 standard CT ratio on the primary side(20 KV) .
Determine the CT primary current.
Substitute 250 A for and 300/5 for CT into equation (2).
Therefore, the value of CT primary current , is .
Similarly, determine the transformer secondary rated current.
Substitute for CT() and for CT(Y) .
Therefore, the value of transformer secondary rated current, is 577.4 A .
Choose a 600:5 standard CT ratio on the secondary side (8.66 KV).
Determine the CT secondary current .
Substitute 577.4 A for I2RATED and 600/5 for CT into equation (3).
Therefore, the value of CT secondary current ,I2 'is 4.811 .
To balance currents in the restraining windings, use certain relay taps.
Determine the ratio of the currents in the restraining winding is:
The closest relay tap ratio is 1:10 , so,
Here, and are the taps of the current transformer.
Therefore, the relay tap ratio is 1:10 and CT ratio is5:55 .
Determine the percentage mismatch for the tap setting ratio .
Substitute 4.167 A for , 4.811 A for , 5 for T1 'and 5:5 for T2' into equation (5).
Therefore, the value of percentage mismatch is -4.7% .