Chapter 10: Q24P (page 665)
Question:Select such that the differential relay characteristic shown in Figure 10.34 blocks for up to 20% mismatch between I1 and I2 .
Short Answer
Answer
The value of k is 0.1818 .
Chapter 10: Q24P (page 665)
Question:Select such that the differential relay characteristic shown in Figure 10.34 blocks for up to 20% mismatch between I1 and I2 .
Answer
The value of k is 0.1818 .
All the tools & learning materials you need for study success - in one app.
Get started for freeIn addition to the costs of the relays, what other costs should be considered when upgrading relays?
An overcurrent relay set to operate at is connected to the CT in Figure 10.8 with a CT ratio. Determine the minimum primary fault current that the relay will detect if the burden is (a), (b) , and (c).
Question: A three-phase 34.5 KV feeder supplying a load 3.5 MVA is protected by 80E power fuses in each phase, in series with a recloser. The time-current characteristic of the fuse is shown in Figure 10.43. Analysis yields maximum and minimum fault currents of 1000 and 500 A, respectively, (a) To have the recloser clear the fault, find the maximum clearing time necessary for recloser operation. (b) To have the fuses clear the fault, find the minimum recloser clearing time. Assume that the recloser operating time is independent of fault current magnitude.
The relay in Problem has a time-dial setting of . Determine the relay operating time if the primary fault current is.
(a) Draw the protective zones for the power system shown in Figure 10.45. Which circuit breakers should open for a fault at (a) , (b) , and (c) ?