Warning: foreach() argument must be of type array|object, bool given in /var/www/html/web/app/themes/studypress-core-theme/template-parts/header/mobile-offcanvas.php on line 20

A simple system with circuit breaker-relay locations is shown in Figure 10.49. The six transmission-line circuit breakers are controlled by zone distance and directional relays, as shown in Figure 10.50. The three transmission lines have the same positive-sequence impedance of j0.1 per unit. The reaches for zones 1, 2 and 3 are 80, 120 and 250% , respectively. Consider only three-phase faults. (a) Find the settings Zrin per unit for all distance relays. (b) Convert the settings in V if the VTs are rated 133 kV : 115 V and the CTs are rated 400 : 5 A. (c) For a fault at location X, which is 10% down line TL31 from bus 3, discuss relay operations.

Figure 10.49

Figure 10.50

Short Answer

Expert verified

Answer

(a)

The value of zone Zrin per unit for zone 1 is 0.08 per unit.

The value of zone Zrin per unit for zone 2 is 0.12 per unit.

The value of zone Zrin per unit for zone 3 is 0.25 per unit.

(b)

The value of zone Zrin terms of the ohms for zone 1 is 2.93Ω.

The value of zone Zrin terms of the ohms for zone 2 is4.39Ω

.

The value of zone Zrin terms of the ohms for zone 3 is9.15Ω.

(c) The issue is located 10% of the way along line TL31 from bus 3. In below Figure depicts the working region for a three-zone distance relay with directional constraint according to the setup.

Step by step solution

01

Write the given data from the question.

Refer to figure 10.49 from the textbook.

Consider the three transmission lines have the same positive-sequence impedance of j0.1 per unit.

Consider the value of zone 1, 2 and 3 reaches at 80%, 120% and 250%.

Consider the value of VTs rated at 133 kV: 115 V.

Consider the value of CTs rated at 400:5 A.

02

Determine the formula of zones settings in per unit, zones settings in ohm.

Write the formula of zone settings Zrin per unit.

…… (1)

Here, Z represent the per unit impedance of the transmission line.

Write the formula of zone settings Zrin ohms.

role="math" localid="1656327151654" 0(Zr)Zr=Zbase …… (2)

Here, Zris a zone setting in per unit and Zbaseis base impedance.

03

(a) Determine the zone settings (Zr) in per unit.

Determine the value of zone 1 reaches at 80%.

Substitute j0.1 for Z and 0.8 for percentage of reach into equation (1).

Zr=0.10.8=0.08perunit

Therefore, the zone Zrin per unit for zone 1 is 0.08 per unit

Determine the value of zone 2 reaches at 120%.

Substitute j0.1for Z and 1.2 for percentage of reach into equation (1).

Zr=0.11.20=0.12perunit

Therefore, the zone Zrin per unit for zone 2 is 0.12 per unit

Determine the value of zone 3 reaches at 250%.

Substitute j0.1for Z and 2.5for percentage of reach into equation (1).

Zr=0.12.5=0.25perunit

Therefore, the zone in per unit for zone 3 is 0.25 per unit

04

(b) Construct the zone settings (Zr) in ohms.

The voltage turn’s ratio of the transformer is 133 kV:115 V and the current ratio of the transformer is 400 : 5 A.

Let's pretend that the system in Figure 1 has a base MVA of MVAbase=100MVAand a base line-to-line voltage ofVLL.base=230kV.

Determine the expression for the base line-to-neutral voltage of the system.

VLNbase=VLLbase3

Here, VLLbaseis base line-to-line voltage.

Substitute 230 kVfor VLLbaseinto above equation.

VLNbase=230kV3=132.79kV

Therefore, the base line-to-neutral voltage VLNbaseis 132.79 kV.

Determine the equivalent transformer secondary voltage for the system.

Vbase=132.79kV115V133kV=132.79kV0.86×10-3=114.82V

Therefore, the equivalent transformer secondary voltage Vbaseis114.82 V.

Determine the base line current flowing in the system.

IL.base=MVAbase3VLLbase

Here, MVAbaseis base MVA and VLLbaseis base line-to-line voltage.

Substitute 230 kV for VLLbaseand 100 MVA for MVAbaseinto above equation.

ILbase=100×1063230×103=100×106398.37×103=251.02A

Therefore, the line base line current, Ibaseis 251.02 A.

Determine the equivalent transformer secondary current for the given system.

Ibase=251.025400=251.020.0125=3.138A

Therefore, the equivalent transformer secondary current, Ibaseis 3.138 A.

Determine the equivalent base impedance of the system.

Zbase=VbaseIbase

Here, Vbaseis equivalent transformer secondary voltage and Ibaseis equivalent transformer secondary current.

Substitute 114.82 V forVbaseand 3.138 A for Ibaseinto above equation.

Zbase=114.823.138=36.59Ω

Therefore, the base impedance, Zbaseof the system is36.59Ω.

Determine the value of zone Zrin terms of the ohms for zone.

Substitute 0.08 for Zrand 36.59Ωfor Zbaseinto equation (2).

ZrΩ=0.0836.59=2.93Ω

Therefore, the settings for the zone 1, ZrΩin terms of the ohms is2.93Ω.

Determine the value of zone Zrin terms of the ohms for zone 2.

Substitute 0.12 for Zrand 36.59Ωfor Zbaseinto equation (2).

ZrΩ=0.1236.59=4.39Ω

Therefore, the settings for the zone 2, ZrΩin terms of the ohms is4.39Ω.

Determine the value of zone Zrin terms of the ohms for zone 3.

Substitute 0.25 for Zrand 36.59Ωfor Zbaseinto equation (2).

ZrΩ=0.2536.59=9.15Ω

Therefore, the settings for the zone 3, ZrΩin terms of the ohms is9.15Ω.

05

(c) Discuss relay operations.

The issue is located 10% of the way along line TL31 from bus 3. In below Figure depicts the working region for a three-zone distance relay with directional constraint according to the setup.

Load currents are often less than fault currents during normal operation. As a result, as illustrated in Figure 3, the system's impedance will be greater beyond the circle.

Figure 1

Determine line breaker operations:

B31: When a failure occurs in zone 1, immediate action is taken.

B32: Directional unit should block operation.

B23: For a fault in Zone 2; delayed operation takes place.

B31: Should trip first, preventing B23from tripping.

B21: Fault duty is light.

B12: Directional unit should block operation.

B13: Fault in Zone 2, just outside of Zone 1, Delayed operation takes place.

The fault is cleared as requested using line breakers B13 and B31. Breakers B1 and B4 must work along with Breaker B13. From quickest to slowest, the trip sequence should be B13, B1, and B4; similarly, B23, B31, and B23 should be quicker than B2 and B5.

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

A CT with an excitation curve given in Figure 10.39 has a rated current ratio of 500 : 5 A and a secondary leakage impedance of 0.1+j0.5Ω. Calculate the CT secondary output current and the CT error for the following cases: (a) The impedance of the terminating device is 4.0+j0.5Ωand the primary CT load current is 400 A. (b) The impedance of the terminating device is 4.0+j0.5Ωand the primary CT fault current is 1200 A. (c) The impedance of the terminating device is 14.9+j1.5Ωand the primary CT load current is 400 A. (d) The impedance of the terminating device is 14.9+j1.5Ωand the primary CT fault current is 1200 A.

A CO-8 relay with a current tap setting of 5 amperes is used with the 100:5 CT in Example 10.1. The CT secondary currentI' is the input to the relay operating coil. The CO-8 relay burden is shown in the following table for various relay input currents.

CO-8 relay Input current I',A

5

8

10

13

15

CO-8 relay burden

ZB,Ω

0.5

0.8

1.0

1.3

1.5

Primary current and CT error are computed in Example 10.1 for the5-,8-, and 1 relay input currents. Compute the primary current and CT error for (a)I'=10A and ZB=1.0Ωand for (b) I'=13Aand ZB=1.3Ω. (c) PlotI' versusI for the above five values of I'. (d) For reliable relay operation, the fault-to-pickup current ratio with minimum fault current should be greater than two. Determine the minimum fault current for application of this CT and relay with5-A tap setting.

CT equivalent circuit.

What is the normal lifetime of a numeric relay? What is the basis of numeric relay lifetime?

Using the current tap settings and time dial settings that you have selected in Problem 10.12, evaluate relay coordination for the minimum fault currents. Are the fault-to-pickup current ratios2.0, and are the coordination time delays 0.3seconds in all cases?

Repeat Example 10.4 for the following system data. Coordinate therelays for the maximum fault currents.

Bus

Maximum Load

Symmetrical fault current

MVA

Lagging P. F

MaximumA

MinimumA
1

9.0

0.95

5000

3750
2

9.0

0.95

3000

2250
3

9.0

0.95

2000

1500

Breaker

Breaker operating Time

CT ratio

Relay

B1

5 cycles

600:5

CO-8

B2

5 cycles

400:5

CO-8

B3

5 cycles

200:5

CO-8

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free