Warning: foreach() argument must be of type array|object, bool given in /var/www/html/web/app/themes/studypress-core-theme/template-parts/header/mobile-offcanvas.php on line 20

Line impedances for the power system shown in Figure 10.47 areZ12=Z23=3.0+j40.0, and Z24=6.0+j80.0. Reach for the zone 3B12 impedance a relay is set for 100% of line 1-2 plus 120% of line 2-4. (a) For a bolted three-phase fault at bus 4, show that the apparent primary impedance “seen” by the B12 relays is

Zapparent=Z12+Z24+(I32/I12)Z24

Where (I32/I12)is the line 2-3 to line 1-2 fault current ratio. (b) If |I32||I12|, does the B12 relay see the fault at bus 4? Note: This problem illustrates the “infeed effect.” Fault currents from line 2-3 can cause the zone 3 B12relay to under reach. As such, remote backup of line 2-4 at B12is ineffective.

Figure 10.47

Short Answer

Expert verified

Answer

(a) The value of apparent primary impedance seen by the B12 relay is calculatedZapparent=Z12+Z24+I32I12×Z24.

(b)

The value of secondary apparent impedance seen by B12 relay isZapparenr=9+6×I32I12+j120+80×I32I12nvnI.

The value of secondary impedance Zt3for B12 set relay isZt3=10.2+j136nvnI.

Step by step solution

01

Write the given data from the question.

The value of line impedance, Z12=3+j40Ω.

The value of line impedance, Z23=3+j40Ω.

The value of line impedance, Z24=6+j80Ω.

Reach for zone 3 B12 impedance relay is 100% for line 1-2.

Reach for zone 3 B12 impedance relay is 120% for line 2-4.

02

Determine the formula of apparent primary impedance seen by the  relay is calculated.

Write the formula of apparent primary impedance seen by the B12 relay is calculated B12.

Zapprent=V1I12 …… (1)

Here,V1is voltage andI12is current.

Write the formula of secondary apparent impedance seen by B12relay.

Zapparent=Zapparent(nvnI) …… (2)

Here, Zapparentis apparent primary impedance nvis VT ratio and nIis CT ratio.

03

(a) Determine the value of apparent primary impedance seen by the  relay is calculated.

Draw a circuit diagram of breakers and impedance relays for the system below.

Figure 1

Draw a circuit diagram for a three phase bolted three phase fault at bus 4:

Figure 2

Determine the apparent primary impedance seen by the B12 relay is calculated B12.

Substitute V1-V2+V2for V1and I12for I12into equation (1).

Zapparent=V1-V2+V2I12=V1-V2I12+V2I12=Z12+V2I12

From figure 2,

Determine the voltageV2.

V2=Z12×I24

Determine the currentI24.

I24=I24+I32

So, solve further as apparent impedance is determine below.

Zapparent=Z12+Z24×I12+I32I12=Z12+Z24+I32I12×Z24

As a result, this is the same as the phrase that must be proven, hence it is proved.

04

(b) Determine the value of secondary apparent impedance seen by  relay.

Determine the secondary apparent impedance.

Zapparcent=Z12+Z24+I32I12×Z24nvnI=3+j40+6+j80+I32I12×Z24nvnIΩ=9+6×I32I12+j120+80×I32I12nvnIΩ …… (3)

The relay is set B12 with secondary impedance .

Zt3=3+j40+1.2×6+j80nvnI=10.2+j136nvnI …… (4)

WhenI32I12>0.20, the relay impedance setting is larger than the apparent impedance, as shown in equations (3) and (4). WhenI32I12>0.20, the apparent impedance is outside the trip zone.

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

Question:Determine the CT ratios for differential protection of a three-phase,Δ--Y connected,10-MVA,33:11 KV , transformer, such that the circulating current in the transformer D does not exceed 5A .

A CT with an excitation curve given in Figure 10.39 has a rated current ratio of500:5Aand a secondary leakage impedance of 1+j0.5. Calculate the CT secondary output current and the CT error for the following cases: (a) The impedance of the terminating device is 9+j0.5and the primary CT load current is 400A. (b) The impedance of the terminating device is 9+j0.5and the primary CT fault current is 1200A. (c) The impedance of the terminating device is 4.9+j1.5and the primary CT load current is 400A. (d) The impedance of the terminating device is role="math" localid="1655725625321" 4.9+j1.5and the primary CT fault current is1200A



.

Reconsider case (b) of Problem 10.5. Let the load impedance be the input impedance to a CO-7 induction disc time-delay overcurrent relay. The CO-7 relay characteristic is shown in Figure 10.41. For a tap setting of and a time dial setting of , determine the relay operating time.

Question:A three-phase, 500 MVA ,345 KV/500 KV transformer is protected by differential relays with taps. Select CT ratios, CT connections, and relay tap settings. Determine the currents in the transformer and in the CTs at rated conditions. Also determine the percentage mismatch for the selected relay tap settings. Available relay tap settings are given in Problem 10.26.

The relay in Problem 10.2has a time-dial setting of 4. Determine the relay operating time if the primary fault current is400A.

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free