Chapter 10: Q17P (page 660)
For the system shown in Figure 10.44, directional overcurrent relays are used at breakers B12, B21, B23, B32, B34, and B43. Overcurrent relays alone are used at B1 and B4. (a) For a fault at P1, which breakers do not operate? Which breakers should be coordinated? Repeat (a) for a fault at (b) P2, (c) P3. (d) Explain how the system is protected against bus faults.
Short Answer
Answer
(a) For fault at P1, the breakers B12, B21, B23 and B32 do not operates.
(b) For fault at P2, the breakers B12, B21, B34 and B43 do not operates.
(c) For fault at P3, the breakers B23, B32, B34 and B43 do not operates.
(d) The system protection, with respect to the fault on the various buses.
Fault bus | Breaker operates |
1 | B1 and B21 |
2 | B12 and B32 |
3 | B23 and B43 |
4 | B4 and B34 |