For the system shown in Figure 10.44, directional overcurrent relays are used at breakers B12, B21, B23, B32, B34, and B43. Overcurrent relays alone are used at B1 and B4. (a) For a fault at P1, which breakers do not operate? Which breakers should be coordinated? Repeat (a) for a fault at (b) P2, (c) P3. (d) Explain how the system is protected against bus faults.

Short Answer

Expert verified

Answer

(a) For fault at P1, the breakers B12, B21, B23 and B32 do not operates.

(b) For fault at P2, the breakers B12, B21, B34 and B43 do not operates.

(c) For fault at P3, the breakers B23, B32, B34 and B43 do not operates.

(d) The system protection, with respect to the fault on the various buses.

Fault bus

Breaker operates

1

B1 and B21

2

B12 and B32

3

B23 and B43

4

B4 and B34

Step by step solution

01

Write the given data from the question:

The directional overcurrent relay B12, B21, B23, B32, B34 and B43 are used at breakers.

The Overcurrent relay B1 and B4 are used alone in the given system.

02

Which overcurrent relay do not operate when fault occurred at P1.

(a)

The breakers under the protection zone P1 are B34 and B43.

For the fault at P1, the breaker under the protection zone P1, B34 and B43 operate and other do not operate. The breaker B34 coordinates with B23, B12 and B1. If the breaker B34 fails to operate under the fault condition only that situation other breaker operate in the same sequence.

Similarly, breaker B43 coordinates with B4. Breaker B4 operate only after the failure of breaker B43.

Therefore, for the fault at P1, the breakers B34 and B43 will operate.

Hence, for fault at P1, the breakers B12, B21, B23 and B32 do not operates.

03

Which overcurrent relay do not operate when fault occurred at P2.

(b)

The breakers under the protection zone P2 are B23 and B32.

For the fault at P2, the breaker under the protection zone P2, B23 and B32 operate and other do not operate. The breaker B23 coordinates with B12 and B1. If the breaker B23 fails to operate under the fault condition only that situation other breaker operate in the same sequence.

Similarly, breaker B32 coordinates with B43 and B4. Breaker B43 and B4 operate only after the failure of breaker B32.

Therefore, for the fault at P2, the breakers B23 and B32 will operate.

Hence, for fault at P2, the breakers B12, B21, B34 and B43 do not operates.

04

Which overcurrent relay do not operate when fault occurred at P3.

(c)

The breakers under the protection zone P3 are B12 and B21.

For the fault at P3, the breaker under the protection zone P3, B12 and B21 operate and other do not operate. The breaker B21 coordinates with B32, B43 and B4. If the breaker B21 fails to operate under the fault condition only that situation other breaker operate in the same sequence.

Similarly, breaker B12 coordinates with B1. Breaker B1 operate only after the failure of breaker B12.

Therefore, for the fault at P3, the breakers B12 and B21 will operate.

Hence, for fault at P3, the breakers B23, B32, B34 and B43 do not operates.

05

Determine the system protection with respect to fault on various buses.

(d)

The following table shows how the system protection works with respect to the fault on the various buses.

Fault bus

Breaker operates

1

B1 and B21

2

B12 and B32

3

B23 and B43

4

B4 and B34

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

Given the open-delta VT connection shown in Figure 10.38, both VTs having a voltage rating of 240kV:120V, the voltages are specified as VAB=230โˆ 0ยฐ,VBC=230ยฐโˆ 120ยฐ,role="math" localid="1655396371549" VBC=230โˆ -120ยฐand VBC=230โˆ 120ยฐ. Determine Vab,Vbcand Vcafor the following cases: (a) The dots are shown in Figure 10.38. (b) The dot near c is moved to b in Figure 10.38.


Question:Consider a three-phase ฮ”--Y connected, 30-MVA,33:11KV , transformer with differential relay protection. If the CT ratios are 500:5A on the primary side and 2000:5A on the secondary side, compute the relay current setting for faults drawing up to 200% of rated transformer current.

An RC circuit used to produce time delay is shown in Figure 10.40. For a step input voltage VI(t)=2u(t)and C=10ฮผF, determine Tdelayfor the following cases: (a) R=100kฮฉand (b) R=1Mฮฉ. Sketch the output V0(t)versus time for cases (a) and (b).

The primary conductor in Figure 10.2 is one phase of a three-phase transmission line operating at345โ€‰kV , 700โ€‰MVA,0.95 power factor lagging. The CT ratio is 1200:5, and the VT ratio is 3000:1. Determine the CT secondary currentI' and the VT secondary voltageV' . Assume zero CT error.

Evaluate relay coordination for the minimum fault currents in Example 10.4. For the selected current tap settings and time dial settings, (a) determine the operating time of relays at B2 and B3 for the 700 A fault current. (b) Determine the operating time of relays at Bl and B2 for the 1500 A fault current. Are the fault-to-pickup current ratios โ‰ฅ2.0(a requirement for reliable relay operation) in all cases? Are the coordination time intervals โ‰ฅ0.3seconds in all cases?

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free