Warning: foreach() argument must be of type array|object, bool given in /var/www/html/web/app/themes/studypress-core-theme/template-parts/header/mobile-offcanvas.php on line 20

A three-phase 34.5 kV feeder supplying a 3.5 MVA load is protected by 80E power fuses in each phase, in series with a recloser. The time-current characteristic of the 80E fuse is shown in Figure 10.43. Analysis yields maximum and minimum fault currents of 1000 and 500 A, respectively, (a) To have the recloser clear the fault, find the maximum clearing time necessary for recloser operation. (b) To have the fuses clear the fault, find the minimum recloser clearing time. Assume that the recloser operating time is independent of fault current magnitude.

Short Answer

Expert verified

(a) The maximum clearing time to clear the fault is 0.137 s.

(b) The minimum clearing time to clear the fault of the recloser is 0.063 s.

Step by step solution

01

Write the given data from the question.

The three-phase voltage, V = 34.5kV

The load S = 3.5 MVA.

The maximum fault current Imax= 1000 A.

The minimum fault current Imin = 500 A.

02

Determine the maximum time required to clear the fault by the recloser.

If the maximum fault current flows through the fuse for a long time, then the material of the fuse get melts. Therefore, the maximum time of clearing the fault should be less than the minimum melting time for the fuse.

The minimum melting time can be obtained corresponding to the minimum fault current, i.e. 500 A.

From the time-current characteristics of the fuse 80E, the maximum time corresponding to the 500 A is 0.135 s.

Hence, the maximum clearing time to clear the fault is 0.137 s.

03

Determine the minimum time required to clear the fault by the recloser.

For clearing the fault by the fuse, the fuse must melt before the recloser opens. The minimum clearing time for the recloser should be greater than the maximum time for the fuse. The fuse's maximum time can be calculated corresponding to the maximum fault current, i.e., 1000 A.

From the time-current characteristics, the maximum clearing for the recloser is 0.063 s.

Hence, the minimum clearing time to clear the fault of the recloser is 0.063 s.

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

A CT with an excitation curve given in Figure 10.39 has a rated current ratio of500:5Aand a secondary leakage impedance of โˆ…1+j0.5. Calculate the CT secondary output current and the CT error for the following cases: (a) The impedance of the terminating device is โˆ…9+j0.5and the primary CT load current is 400A. (b) The impedance of the terminating device is โˆ…9+j0.5and the primary CT fault current is 1200A. (c) The impedance of the terminating device is โˆ…4.9+j1.5and the primary CT load current is 400A. (d) The impedance of the terminating device is role="math" localid="1655725625321" โˆ…4.9+j1.5and the primary CT fault current is1200A



.

A simple system with circuit breaker-relay locations is shown in Figure 10.49. The six transmission-line circuit breakers are controlled by zone distance and directional relays, as shown in Figure 10.50. The three transmission lines have the same positive-sequence impedance of j0.1 per unit. The reaches for zones 1, 2 and 3 are 80, 120 and 250% , respectively. Consider only three-phase faults. (a) Find the settings Zrin per unit for all distance relays. (b) Convert the settings in V if the VTs are rated 133 kV : 115 V and the CTs are rated 400 : 5 A. (c) For a fault at location X, which is 10% down line TL31 from bus 3, discuss relay operations.

Figure 10.49

Figure 10.50

The relay in Problem 10.2has a time-dial setting of 4. Determine the relay operating time if the primary fault current is400A.

Line impedances for the power system shown in Figure 10.47 areZ12=Z23=3.0+j40.0, and Z24=6.0+j80.0. Reach for the zone 3B12 impedance a relay is set for 100% of line 1-2 plus 120% of line 2-4. (a) For a bolted three-phase fault at bus 4, show that the apparent primary impedance โ€œseenโ€ by the B12 relays is

Zapparent=Z12+Z24+(I32/I12)Z24

Where (I32/I12)is the line 2-3 to line 1-2 fault current ratio. (b) If |I32||I12|, does the B12 relay see the fault at bus 4? Note: This problem illustrates the โ€œinfeed effect.โ€ Fault currents from line 2-3 can cause the zone 3 B12relay to under reach. As such, remote backup of line 2-4 at B12is ineffective.

Figure 10.47

The CT of Problem 10.5is utilized in conjunction with a current sensitive device that will operate at current levels of role="math" localid="1655405578534" 8Aor above. Check whether the device will detect the 1300Afault current for cases (b) and (d) in Problem 10.5.

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free