Warning: foreach() argument must be of type array|object, bool given in /var/www/html/web/app/themes/studypress-core-theme/template-parts/header/mobile-offcanvas.php on line 20

Question:Determine the CT ratios for differential protection of a three-phase,Δ--Y connected,10-MVA,33:11 KV , transformer, such that the circulating current in the transformer D does not exceed 5A .

Short Answer

Expert verified

Answer

The value of the CT ratio for the differential protection of a three phase is .

Step by step solution

01

Write the given data from the question

Consider the value of base MVA is 10 .

Consider the value of three-phase voltage ratio is 33;11 KV.

Consider circulating current is 5 A.

02

Determine the formula of CT ratio for the differential protection of a three phase.

Write the formula ofCT ratio on HV side is,

CTratioHV=I25 …… (1)

Here, I1 is line current of secondary side.

Write the formula of CT ratio on LV side is,

CTratioLV=I15 …… (2)

Here, I2 is line current of primary side.

03

 Determine the value of CT ratio for the differential protection of a three phase.

Determine the line current in the primary side (delta side).

I1=10×106333×103=174.95A

Determine the line current in the secondary side (star side).

I2=10×106311×103=524.86A

Therefore, the HV side is connected in delta, so the CTs on HV side are connected in star.

Determine the circulating current should not exceed. So, the CT ratio on HV side.

Substitute 524.86 for I2 into equation (1).

CTratioHV=524.865=104.97

Similarly, the CT ratio on LV side.

Substitute 174.953For I1 into equation (2).

CTratioLV=174.9535=60.6

Therefore,the value of the CT ratio for the differential protection of a three phase is 60.6 .

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

A CT with an excitation curve given in Figure 10.39 has a rated current ratio of 500 : 5 A and a secondary leakage impedance of 0.1+j0.5Ω. Calculate the CT secondary output current and the CT error for the following cases: (a) The impedance of the terminating device is 4.0+j0.5Ωand the primary CT load current is 400 A. (b) The impedance of the terminating device is 4.0+j0.5Ωand the primary CT fault current is 1200 A. (c) The impedance of the terminating device is 14.9+j1.5Ωand the primary CT load current is 400 A. (d) The impedance of the terminating device is 14.9+j1.5Ωand the primary CT fault current is 1200 A.

Question:Consider a three-phase Δ--Y connected, 30-MVA,33:11KV , transformer with differential relay protection. If the CT ratios are 500:5A on the primary side and 2000:5A on the secondary side, compute the relay current setting for faults drawing up to 200% of rated transformer current.

Question: A three-phase 34.5 KV feeder supplying a load 3.5 MVA is protected by 80E power fuses in each phase, in series with a recloser. The time-current characteristic of the fuse is shown in Figure 10.43. Analysis yields maximum and minimum fault currents of 1000 and 500 A, respectively, (a) To have the recloser clear the fault, find the maximum clearing time necessary for recloser operation. (b) To have the fuses clear the fault, find the minimum recloser clearing time. Assume that the recloser operating time is independent of fault current magnitude.

Question:A single-phase, 5 MVA 20/8.66 KV , transformer is protected by a differential relay with taps. Available relay tap settings are 5:5,5:55,5:66 , 5:73 , 5:8 ,5:9 ,and 5:10, giving tap ratios of 1,1:10,1:32,1:46.1:60,1:80, and 2:00. Select CT ratios and relay tap settings. Also, determine the percentage mismatch for the selected tap setting.

Question:Consider a protected bus that terminates four lines, as shown in Figure 10.51. Assume that the linear couplers have the standard and a three-phase fault externally located on line causes the fault currents shown in Figure 10.51. Note that the infeed current on line to the fault is . (a) Determine . (b) Let the fault be moved to an internal location on the protected bus between lines and . Find and discuss what happens. (c) By moving the external fault from line to a corresponding point on (i) line and (ii) line , determine in each case.

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free