Calculate the base current,
Substitute 60 MVA for and 15 kV for into equation (1).
The pre fault circuit is shown below.

The post fault circuit is shown below.

Calculate the fault current.
Substitute 14.5 kV forand 15 kV for into equation (2).
Calculate the motor current.
Substitute 40 MW for , 0.8 for, 14.5 kV for and 0.8 for into equation (3).
Calculate the motor current in per unit.
Calculate the terminal voltage for generator.
Substitute 0.967 pu for , forinto equation (4).
Calculate the induced voltage for generator.
Substitute for , forinto equation (5).
Calculate the sub transient generator current.
Substitute for localid="1655889139996" forand forinto equation (6).
Calculate the sub transient generator current in per unit value.
Calculate the terminal voltage for motor.
Substitute 0.967 pu for into equation (7).
Calculate the induced voltage for motor.
Substitute 0.967 pu for forinto equation (8).
Calculate the sub transient motor current.
Substitute for and for into equation (9).
Calculate the sub transient motor current in per unit value.
Calculate the sub transient current for three phase faults.
Substitute for , and for into equation (10).
localid="1655889009222"
Hence, the subs transient current in generator, motor and the fault are respectively.