Determine the power angle.
The negative sign shows the power factor is lagging in nature.
Determine the actual generator current.
…… (6)
Here, S is bus voltage,is full load voltage and V is base generator voltage.
Substitute for S, 1.05 for and for V into equation (6).
Determine the base current.
…… (7)
Substitute for Base MVA and for Base generator voltage into equation (7).
Determine the actual generator current per unit.
…… (8)
Here, is actual generator current and is base current.
Substitute for and for into equation (8).
Determine the base reactance of the system.
…… (9)
Here, kV is generator base voltage and MVA is base MVA of generator.
Substitute for kV and for MVA into equation (9).
Determine the line reactance per unit.
…… (10)
Here, is line reactance and is base reactance.
Substitute 20 for and 190.44 for into equation (10).
Draw a diagram of synchronous generator where fault occurs at bus 1 of feeding the motor.

Figure 1
Determine the internal machine per unit voltage of behind generator.
Substitute 1.05 for , 0.9046-0.2974 for and 0.15 for into equation (1).
Determine the internal machine per unit voltage of behind motor.
Substitute 1.05 for , 0.9046-j0.2974 for and 0.505 for into equation (2).