Determine the value of current in phase domain for single line-to-ground fault from figure1.
Determine the value of voltage in phase domain for single line-to-ground fault from figure1.
…… (2)
Here, is fault impedance and is phase current.
Determine the expression for sequence currents.
role="math" localid="1656160355486"
Here, , and are the phase currents.
The value ofandis,
Substitute for , for into above equation.
Determine the expression for sequence voltages.
Here, ,and are the phase voltages.
Determine the expression for phase- voltage.
Substitute for role="math" localid="1656160842493" and for into equation (2).
Determine the value of current in sequence domain for single line-to-ground fault from figure 2.
Determine the value of voltage in sequence domain for single line-to-ground fault from figure 2.
Determine the zero sequence current expression from figure 2.
Here, is fault voltage,is positive sequence component,is positive sequence component andis negative sequence component andis fault impedance.
Determine the expression of fault current in phase .
Therefore, all sequence currents are same.
Substituteforand forinto equation (1).
…… (3)
Substitute for into equation (3)
Hence, the expression for the fault current in phase is .