Calculate the impedance of -connected load from -connected load.
Substitutefor into equation (1).
Calculate the per phase voltage.
Substituteforinto equation (2).
Since the supply and the load are balanced, the zero and negative sequence network will not have the source voltage, and only the positive sequence network will have the source voltage.
The load is connected into delta and the neutral will be open. Therefore, open circuit will be there in the load side zero sequence network. The generator is grounded with the impedance of .There will be impedance ofthe source side zero sequence network.
Therefore, the zero-sequence impedance is shown below.

Therefore, the negative sequence impedance is shown below.\

Calculate the positive sequence terminal voltage.
Therefore, the positive sequence impedance is shown below.

Apply the Kirchhoff’s voltage law in positive sequence network.
Substitute forinto above equation.
Calculate the positive sequence component of the line current
Substitutefor,forandinto equation(3).
Hence the positive sequence component of the line current is.