In a balanced three-phase system, what is the zero-sequence voltage? V0= _______________

Short Answer

Expert verified

In a balanced three-phase system, what is the zero-sequence voltage?V0=0volts

Step by step solution

01

Symmetrical Component

There are three-phases of symmetrical component power system which are resolved into three sets of sequential components such as: Positive-sequence, Negative-sequence and Zero-sequence component.

02

Determine the answer

Write the general formula for zero sequence voltage.

V0=Va+Vb+Vc3

The sum of all the voltages is equal to zero in a balanced three phase system.

Therefore,Va+Vb+Vc=0

Thus, calculate the zero sequence voltage is in a balanced system by substituting 0 for Va+Vb+Vc

V0=03=0V

Hence, the zero sequence voltage is in a balanced system is 0volts.

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

A completely transposed three-phase transmission line of 200kmin length has the following symmetrical sequence impedances and sequence admittances:

Z1=Z2=j0.5ΩkmZ0=j2ΩkmY1=Y2=j3×10-9smY0=j1×10-9smSetupthenominalπsequencecircuitsofthismedium-lengthline.

Consider the per-unit sequence networks of Y-Y,Y-, and -transformers with neutral impedances of Znon the high-voltage -side and Znon the low-voltage Y-side. Answer the following:

(i) Zero-sequence currents (a) can or (b) cannot flow in the Y winding with a neutral connection; corresponding zero-sequence currents (a) do or (b) do not flow within the delta winding; however, zero sequence current (a) does or (b) does not enter or leave the D winding. In a zero-sequence network, (a) 1, (b) 2, or (c) 3 times the neutral impedance comes into play in series.

(ii) In (HW)-(Y-)transformers, if a phase shift is included as per the American-standard notation, the ratio ___________ is used in positive-sequence network, and ___________ the ratio ___________ is used in the negative-sequence network.

(iii) The base voltages depend on the winding connections; the per-unit impedances (a) do or (b) do not depend on the winding connections.

The three-phase impedance load shown in Figure 8.7 has the following phase impedance matrix:

ZP=5+j100005+j100005+j10

Determine the sequence impedance matrix ZSfor this load. Is the load symmetrical?

Unbalanced three-phase systems may have nonzero values for all sequence components.

(a) True (b) False

A balanced Y-connected generator with terminal voltageVbc=2000°Vvolts is connected to a balanced Δload whose impedance is 1040°ohms per phase. The line impedance between the source and load is 0.580°ohm for each phase. The generator neutral is grounded through an impedance of ohms. The generator sequence impedances are given byZg0=j7, Zg1=j15, andZg2=j10 ohms. Draw the sequence networks for this system and determine the sequence components of the line currents.

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.