Warning: foreach() argument must be of type array|object, bool given in /var/www/html/web/app/themes/studypress-core-theme/template-parts/header/mobile-offcanvas.php on line 20

The motorsM1and M2of Problem 3.45 have inputs of 120 MWand 60 MW, respectively, at 13.2 kV, and both operate at unity power factor. Determine the generator terminal voltage and voltage regulation of the line. Neglect transformer phase shifts.

Short Answer

Expert verified

The voltage regulation is 0.0255 and the voltage at generator terminal is VG=19.652kV.

Step by step solution

01

Given data

The power input to motors M1and M2 is 120 MW and 60 MW .

02

Determine the formulas ofper-unit voltage, power and current.

Write the formula of per-unit voltage.

Vpu=VactualVbase……. (1)

Write the formula of per-unit power

Spu=SoriginalSbase ……. (2)

Write the formula of per-unit power

IpuSpuVpu ……. (3)

03

Determine the per-unit current through motor.

The base voltage at motor bus is Vbase=13.8kVand the actual voltage is Vactual=13.2kV.

So, the per-unit voltage using equation (1) is calculated as,

Vpu=13.2kV13.8kV=0.9565pu

The base power in system is Sbase=300MWand the actual power is Sactual=120+60MW.

So, the per-unit power using equation (2) is calculated as,

Spu=120+60MW300MW=0.6pu

Substitute 0.6puforSpuand0.9565puforVpuin equation (3).

Ipu=0.6pu0.9565pu=0.6273pu

04

Determine the voltage regulation and terminal voltage at generator.

The per-unit impedance of transformer 2 from single-line diagram of problem 3.45 is XT2=0.0915pu, similarly, for transmission line is Xline=0.0915puand transformer 1 is XT1=0.0857pu.

Determine the voltage drop at point m for the above system.

V1=Vpu+jXT2Ipu=0.9565+j0.09150.6273=0.95823.434°pu

Determine the voltage drop at point k for the above system.

V2=Vpu+jXT2+XT1+XlineIpu=0.9565+j0.0915+0.1815+0.08570.6273=0.982613.237°pu

The voltage regulation is calculated as,

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

A single-phase 50kVA,2400/240volt,60Hzdistribution transformer is used as a step-down transformer at the load end of a 2400 volt feeder whose series impedance is(1.0+j2.0)ohm. The equivalent series of the transformer is(1.0+j2.5)ohm referred to the high-voltage (primary) side. The transformer is delivering rated load at a power factor lagging and at a rated secondary voltage. Neglecting the transformer exciting current, determine (a) the voltage at the transformer primary terminals, (b) the voltage at the sending end of the feeder, and (c) the real and reactive power delivered to the sending end of the feeder.

A single-phase 100kVA, 2400/240volts, 60Hzdistribution transformer is used as a step-down transformer. The load, which is connected to the 240voltssecondary winding, absorbs role="math" localid="1655831901768" 60kVAat 0.8 power factor lagging and is at 230volts. Assuming an ideal transformer, calculate the following (a) Primary voltage, (b) load impedance, (c) load impedance referred to the primary, and (d) the real and reactive power supplied to the primary winding.

Consider the single-line diagram of a power system shown in Figure 342 With equipment ratings given:

GeneratorG150MVA,13.2kV,x=0.15p.u

GeneratorG220MVA,13.8kV,x=0.15p.u

Three-phaseΔ-Ytransporter T1:80MVA,13.2Δ/165YkV,X=0.1p.u

Three-phaseY-Δ transformer T2:40MVA,165Y/13.8ΔkV,X=0.1p.u

Load: 40MVA,0.8PF lagging, operating at

150kVA

Choose a base of 100 MVA for the system and 132-kV base in the transmission-line circuit. Let the load be modeled as a parallel combination of resistance and inductance Neglect transformer phase shifts. Draw a per-phase equivalent circuit of the system showing all impedances in per unit.

For an ideal 2-winding transformer, an impedanceZ2connected acrosswinding 2 (secondary) is referred to winding 1 (primary) by multiplying by

(a) The turns ratio(N1N2)
(b) The square of the turn’s ratiorole="math" localid="1655113801735" (N1N2)2
(c) The cubed turn’s ratio(N1N2)3

Rework Problem 3.14 if the transformer is delivering rated load at rated secondary voltage and at (a) unity power factor, (b) 0.8power factor leading. Compare the results with those Of Problem 3.14.

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free