Chapter 3: Q45P (page 153)
Figure 3.39 shows a oneline diagram of a system in which the three-phase generator is rated 300 MVA , 20kV with a sub transient reactance of 2.0 per unit and with its neutral grounded through a 0.4 V reactor. The transmission line is 64 km long with a series reactance of . The three-phase transformer is rated 350 MVA , 230/20kV with a leakage reactance of 0.1 per unit. Transformer is composed of three single-phase transformers,each rated 100 MVA , 127/13.2 kV with a leakage reactance of 0.1 per unit. Two 13.2kV motors and with a sub transient reactance of 0.2 per unit for each motor represent the load. has a rated input of 200 MVA with its neutral grounded through a 0.4 V current-limiting reactor. has a rated input of 100 MVA with its neutral not connected to ground. Neglect phase shifts associated with the transformers. Choose the generator rating as base in the generator circuit and draw the positive-sequence reactance diagram showing all reactance in per unit.
Short Answer
Draw the per-unit single line diagram below: