Chapter 3: Q38P (page 151)
Consider a three-phase generator rated supplying a system load of and 0.9 power factor lagging at through a step-up transformer with a leakage reactanceof 0.11 per unit. (a) Neglecting the exciting current and choosing base values at the load of 100MW and 230kV , find the phasor currents role="math" localid="1655190109478" supplied to the load in per unit. (b) By choosing the load terminalvoltage as reference, specify the proper base for the generator circuitand determine the generator voltageas well as the phasor currentsrole="math" localid="1655190101018" from the generator. (Note:Take into account the phase shift of the transformer.) (c) Find the generator terminal voltage in kV and the real power supplied by the generator in MW . (d) By omitting the transformer phase shift altogether, check to see whether you get the same magnitude ofgenerator terminal voltage and real power delivered by the generator.
Short Answer
(a) The phase currents are
(b) The generator voltage is and the phase currents are
(c) The generator terminal voltage is and the real power supplied by the generator is .
(d) The terminal voltage and power will remain same, if phase shift is omitted.