Warning: foreach() argument must be of type array|object, bool given in /var/www/html/web/app/themes/studypress-core-theme/template-parts/header/mobile-offcanvas.php on line 20

Consider a three-phase generator rated 300MW,23kVsupplying a system load of 240MWand 0.9 power factor lagging at 230kVthrough a 330MW,23/230YkV step-up transformer with a leakage reactanceof 0.11 per unit. (a) Neglecting the exciting current and choosing base values at the load of 100MW and 230kV , find the phasor currents role="math" localid="1655190109478" IA,IBandICsupplied to the load in per unit. (b) By choosing the load terminalvoltage VAas reference, specify the proper base for the generator circuitand determine the generator voltageas well as the phasor currentsrole="math" localid="1655190101018" IA,IBandICfrom the generator. (Note:Take into account the phase shift of the transformer.) (c) Find the generator terminal voltage in kV and the real power supplied by the generator in MW . (d) By omitting the transformer phase shift altogether, check to see whether you get the same magnitude ofgenerator terminal voltage and real power delivered by the generator.

Short Answer

Expert verified

(a) The phase currents areIApu=2.4-25.84°pu,IBpu=2.4-145.84°puandICpu=2.494.16°pu

(b) The generator voltage is VA=130°pu and the phase currents areIapu=2.4-55.84°puandIbpu=2.4-175.84°puandIcpu=2.464.16°pu

(c) The generator terminal voltage is 23.86-26.02°kVand the real power supplied by the generator is 216MW.

(d) The terminal voltage and power will remain same, if phase shift is omitted.

Step by step solution

01

Determine the formulas ofactual current, base current, per-unit current, power angle, per-unit reactance, generator terminal voltage and real power supplied by generator

Write the formula of per-unit current.

IA(pu)=IactualIactual……. (1)

Write the formulas of base current.

role="math" localid="1655190935371" Ibase=Sbase3×Vbase……. (2)

Write the formulas of actual current.

role="math" localid="1655191088960" Iactual=Sactual3×Vactual ……. (3)

Write the formula of power angle.

θ=cos-1(p.f)……. (4)

Write the formula of phase current in phase ‘B’.

IB(pu)=IA(pu)-120° …… (5)

Write the formula of phase current in phase ‘C’.

IC(pu)=IA(pu)120° …… (6)

Write the formula of new reactance of transformer in per-unit.

Xpu(new)=Xpu(new)×Sbase(new)Sbase(old) …… (7)

Write the formula of generator terminal voltage.

Vt=VA-30°+XpuIA …… (8)

Write the formula of real power supplied by generator.

Ppu=VAIa* …… (9)

02

Determine the per-unit phasor currents.

The single-line diagram and the per-phase equivalent circuit, with all parameters in per unit, are given below:

(a)

Substitute 100 M Wfor Sbaseand 230 kVfor Vbasein equation (2).

Ibase=100MW3×230kV=250.02A

Substitute 240 M W for Sactual and 230 kVfor Vactualin equation (3).

Iactual=240MW3×230kV=602.45A

Substitute 602.45 Afor Iactual and 250.02 A for Ibasein equation (1).

IApu=602.45A250.02A=2.4pu

Substitute 0.9for p.fin (4).

θ=cos-10.9=25.84°

Therefore, for lagging load, the current is IApu=2.4-25.84°pu.

The currents in ‘B’ and ‘C’ phases using equations (5) and (6).

IBpu=2.4-120°-25.84°pu=2.4-145.84°pu

Current in phase ‘C’ is,

ICpu=2.4120°-25.84°pu=2.494.16°pu

03

Determine the generator voltage and currents.

(b)

Let, the reference voltage at load in per-unit is VA=10°pu.

The generator voltage leads the load voltage by 30°.

Therefore, the generator voltage will be VA=130°pu.

The generator current lags the load current by 30°.

Therefore, the generator current in phase ‘a’ is,

Iapu=2.4-25.84°-30°pu=2.4-55.84°pu

The generator current in phase ‘b’ is,

Ibpu=2.4-145.84°-30°pu=2.4-175.84°pu

Current in phase ‘c’ is,

Icpu=2.494.16°-30°pu=2.464.16°pu

04

Determine the generator terminal voltage in kV and MW power supplied by generator.

(c)

Determine the new reactance of transformer.

Substitute 0.11puforXpu(old),100MWforSbasenewand330MWforSbaseoldin equation (7).

Xpuold=0.11pu×100330=130pu

Substitute 1-30°puforVA,130puforXpuand2.4-25.84°forIAin equation (8).

Vtpu=1-30°+1302.4-55.84°=1.0374-26.02°pu

The actual generator voltage will be,

Vt=1.0374-26.02°23kV=23.86-26.02°kV

Substitute 1.0374-26.02°puforVtand2.4-55.84°forIA in equation (9).

Ppu=Re1.0374-26.02°pu2.4-55.84°*=2.16pu

The real power in MW is,

P=PbasePpu=100MW×2.16pu=216MW

05

Determine the generator terminal voltage in kV and MW power supplied by generator.

(d)

Determine the generator terminal voltage when phase shift is omitted.

Substitute10°puforVA,130puforXpuand2.4-25.84°forIA in equation (8).

Vtpu=10°+1302.4-55.84°=1.0374-3.62°pu

Therefore, the terminal voltage will be same, and hence power will also same.

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

(a) An ideal single-phase two-winding transformer with turns ratio at=N1N2is connected with a series impedance localid="1656741053389" Z2across winding 2. If one wants to replace localid="1656741059221" Z2with a series impedance localid="1656741063182" Z1across winding 1 and keep the terminal behavior of the two circuits to be identical, find localid="1656741066768" Z1in terms of localid="1656741070118" Z2

(b) Would the above result be true if instead of a series impedance there is a shunt impedance?

(c) Can one refer a ladder network on the secondary (2) side to the primary (1) side simply by multiplying every impedance by localid="1656741074149" at2?

Consider three ideal single-phase transformers (with a voltage gain of η)put together as a -Ωthree-phase bank as shown in Figure 3.35. Assuming positive-sequence voltages forVan,Vbn,andVcn,findVa'n',Vb'n',andVc'n'in terms ofVan,Vbn,andVcn,respectively.

(a) Would such relationships hold for the line voltages as well?

(b) Looking into the current relationships, expressIa',Ib',andIc'in terms

ofIa,Ib,andIc,respectively.

(c) Let S'and Sbe the per-phase complex power output and input,

respectively. Find S'in terms of S.

The direct electrical connection of the windings allows transient overvoltages to pass through the autotransformer more easily, and that is animportant disadvantage of the autotransformer.

(a) True

(b) False

A single-phase transformer has 2000 turns on the primary winding and 500 turns on the secondary. Winding resistances are R1=2Ω,andR2=0.125Ω; leakage reactance’s are X1=8Ω,andX2=0.5Ω.The resistance load on the secondary is 12Ω.

(a) If the applied voltage at the terminals of the primary is 1000V , determine V2 at the load terminals of the transformer, neglecting magnetizing current.

(b) If the voltage regulation is defined as the difference between the voltage magnitude at the load terminals of the transformer at full load and at no load in percent of full-load voltage with input voltage held constant, compute the percent voltage regulation.

Consider Figure 3.10 Of the text. The per-unit leakage reactance of transformer T1, given as 0.1p.u, is based on the name plate ratings of transformerT1.

(a) True (b) False

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free