Warning: foreach() argument must be of type array|object, bool given in /var/www/html/web/app/themes/studypress-core-theme/template-parts/header/mobile-offcanvas.php on line 20

For the system shown in Figure 3.34, draw an impedance diagram in per unit by choosing100kVAto be the basekVAand2400Vas the base voltage for the generators.

Short Answer

Expert verified

The per-unit single-line diagram is as follows.

Step by step solution

01

Determine the formulas for base impedance, per-unit impedance, and new value of per-unit impedance.

Write the formula for new per-unit impedance:

Zpe(new)=Zpe(old)Vbase(old)Vbase(new)2Sbase(new)Sbase(old) …… (1)

Write the formula for base impedance:

Zbase=Vbase2Sbase …… (2)

Write the formula for per-unit impedance”

Zpu=ZactualZbase …… (3)

02

Determine the per-unit impedance of generator 1, generator 2, transformer 1, and transformer 2.

The base voltage on generator 1 is Vbase(old)=2400 V.

The new base voltage is Vbase(new)=2400 V.

The old base power on generator 1 is Sbase(old)=10 kVA and the new base power is role="math" localid="1655964231545" Sbase(new)=100 kVA.

Determine the new impedance on generator 1.

Substituting j0.2 pu for ZG1(old), 2400 V for role="math" localid="1655964239799" Vbase(new), 2400 V for role="math" localid="1655964245880" Vbase(old), 100 kVA forrole="math" localid="1655964213660" Sbase(new), and 10 kVA for role="math" localid="1655964219753" Sbase(old) in Equation (1), we have

ZG1(new)=j0.2 pu2400 V2400 V2100 kVA10kVA=j2 pu

Determine the new impedance on generator 2.

Substituting j0.2 pu for ZG2(old), 2400 V for Vbase(new), 2400 V for Vbase(old), 100 kVAfor Sbase(new), and 20 kVAfor Sbase(old) in Equation (1), we have

ZG1(new)=j0.2 pu2400 V2400 V2100 kVA10kVA=j2 pu

Determine the new impedance on generator 2.

Substituting j0.2 pufor ZG2(old), 2400 V for Vbase(new), 2400 V for Vbase(old) , 100 kVA for Sbase(new), and 20 kVA for Sbase(old) in Equation (1), we have

ZG2(new)=j0.2 pu2400 V2400 V2100 kVA20kVA=j1 pu

Determine the new impedance on transformer 1.

Substituting j0.1 pu for ZT1(old), 2400 V for Vbase(new), 2400 V for Vbase(old), 100 kVA for Sbase(new), and 40 kVAfor Sbase(old)in Equation (1), we have

ZT1(new)=j0.1 pu2400 V2400 V2100 kVA40kVA=j0.25 pu

Determine the new impedance on transformer 2.

Substituting j0.1 pu for ZT2(old),9.6 kVfor Vbase(new), 10 kV for Vbase(old), 100 kVA for Sbase(new), and 80 kVA for Sbase(old) in Equation (1), we have

ZT2(new)=j0.1 pu10 kV9.6 kV2100 kVA80kVA=j0.136 pu

03

Draw the per-unit single-line diagram.

Determine the base impedance on line.

Substituting9.6 kVfor Vbase and for in Equation (2), we have

Zbase=96002100×103=921.6Ω

Determine the per-unit impedance on line.

Substituting 921.6Ω for Zbase and(50+j200)Ω for Zactual in Equation (3), we have

Zline(pu)=(50+j200)Ω921.6Ω=0.054+j0.217  pu

Determine the per-unit power and the per-unit voltage on the motor side.

The per-unit voltage is as follows:

VM(pu)=4 kV5 kV=0.8 pu

The per-unit power is as follows:

SM(pu)=25 kVA100kVA=0.25 pu

Therefore, the single-line diagram is as follows:

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

Three single-phase two-winding transformers, each rated 25MVA,54.25.42kV , are connected to form a three-phaseY-Δ bank with a balanced Y-connected resistive load of 0.6Ωper phase on the low-voltage side. By choosing a base of 75MVA (three phase) and 94kV (line-to-line) for the high-voltage side of the transformer bank, specify the base quantities for the low-voltage side. Determine the per-unit resistance of the load on the base for the low-voltage side. Then determine the load resistance in ohms referred to the high-voltage side and the per-unit value of this load resistance on the chosen base

A single-phase two-winding transformer rated 90MVA,80/120kV,is to be connected as an autotransformer rated80/200kV . Assume that the transformer is ideal. (a) Draw a schematic diagram of the ideal transformer connected as an autotransformer, showing the voltages, currents,and dot notation for polarity. (b) Determine the permissible kVA rating of the autotransformer if the winding currents and voltages are not to exceed the rated values as a two-winding transformer. How much of the kVA rating is transferred by magnetic induction?

Answer

A 23/230kVstep-up transformer feeds a three-phase transmission line, which in turn supplies a150MVA,0.8 lagging power factor load through a step-down230/23kV transformer. The impedance of the line and transformers at 230kVis 18+j60Ω. Determine the tap setting for each transformer to maintain the voltage at the load at .

A single-phase 10kVA,2300/230volt,60-Hztwo-winding distribution transformer is connected as an autotransformer to step up the voltage from 2300 to2530volts. (a) Draw a schematic diagram of this arrangement, showing all voltages and currents when delivering full load at rated voltage (b) Find the rating of the autotransformer if the winding currents and voltages are not to exceed the rated values as a two-winding transformer. How much of this kVA rating is transformed by magnetic induction? (c) The following data are obtained from tests carried out on the transformer When it is connected as a two-winding transformer:

Open-circuit test with the low-voltage terminals excited:
Applied voltagelocalid="1656747038872" =230V , input current localid="1656747042832" =4.5A, input power localid="1656747046762" =70W

Short-circuit test with the high-voltage terminals excited:
Applied voltage localid="1656747050183" =120V, input current localid="1656747053614" =4.5A, input power localid="1656747057853" =240W

Based on the data, compute the efficiency of the autotransformer corresponding to full load, rated voltage, andlocalid="1656747062178" 0.8 power factor lagging. Comment on Why the efficiency is higher as an autotransformer than as a two-winding transformer.

Consider the oneline diagram shown in Figure 3.40. The three-phase transformer bank is made up of three identical single-phase transformers,each specified by X1=0.24Ω(on the low-voltage side), negligible resistance and magnetizing current, and turns ratio η=N1N2=10. The transformer bank is delivering 100MWat 0.8 p.f. lagging to a substation bus whose voltage is 230 kV.

(a) Determine the primary current magnitude, primary voltage (line-to-line) magnitude, and the three-phase complex power supplied by the generator. Choose the line-to-neutral voltage at the bus,role="math" localid="1655206659086" Va'n'as the reference. Account for the phase shift, and assume positive-sequence operation.

(b) Find the phase shift between the primary and secondary voltages.

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free