With the American Standard notation, in either a Y-Δ orΔ-Y transformer, positive-sequence quantities on the high-voltage side shall lead their corresponding quantities on the low-voltage side by 30°.

(a) True (b) False

Short Answer

Expert verified

Therefore, the correct option is (a) True.

Step by step solution

01

Draw the phase shifting Y-Δ transformer.

The core arrangement for the phase shiftingYΔ transformer.

Figure for the analysing the angle between the quantities.

02

Determine the phase shift between the high voltage side and low voltage side.

From the figure shown in step 1, it is clear that the voltageVAN&Vab are in the same phase and Vanis lag by30° with respect to Vab. Therefore, the phase shift between the voltageVAN&Van is30° .

Hence,positive-sequence quantities on the high-voltage side shall lead their corresponding quantities on the low-voltage side by 30°.

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

For the transformer in Problem 3.10, the open-circuit test with 11.5kVapplied results in a power input of 65kW and a current of 30A . Compute the values forGcand Bmin siemens referred to the high-voltage winding. Compute the efficiency of the transformer for a load of 10MW at 0.8 p.f. lagging at rated voltage.

Question:Does an openoperation, the kVA rating compared to that of the original three-phase bank is

(a) 2/3

(b) 58%

(c) 1

Consider the single-line diagram of the power system shown inFigure 3.38. Equipment ratings are:

Generator 1:1000MVA,18kV,X''=0.2pu .

Generator 2: 1000MVA,18kV, X''=0.2pu.

Synchronous motor 3: 1500MVA,20kV, X''=0.2pu.

Three-phaseΔ–Y transformers1000MVA,500kVY/20kVΔ, X=0.1pu.

T1,T2,T3, T4, :

Three-phase Y–Y transformerT5: 1500MVA, 500kV/20kV, X=0.1pu

Neglecting resistance, transformer phase shift, and magnetizing reactance, draw the equivalent reactance diagram. Use a base of 100MVAand 500kV for the50Ω line. Determine the per-unit reactances.

Consider Figure 3.25 of the text for a transformer with off-nominal turns ratio.

(i) The per-unit equivalent circuit shown in part (c) contains an ideal transformer which cannot be accommodated by some computer programs.

(a) True

(b) False

(ii) In the- circuit representation for real c in part (d), the admittance parametersandwould be unequal.

(a) True

(b) False

(iii) For complex c, can the admittance parameters be synthesized with a passive RLC circuit?

(a) Yes

(b) No

For an ideal 2-winding transformer, the ampere-turns of the primary winding, N1I1, is equal to the of the secondary winding N2I2,

(a) True