Three single-phase two-winding transformers, each rated , with
a 0.10 per unit leakage reactance, are connected as a three-phase extendedautotransformer bank, as shown in Figure 3.36 The low-voltage A winding has a 110 volt rating. (a) Draw the positive- sequence phasor diagram and show that the high-voltage winding has a 479.5 volt rating. (b) A three-phase load connected to the low-voltage terminals absorbs 6kW at 110 volts
and at 0.8 power factor lagging. Draw the per-unit impedance diagram and calculate the voltage and current at the high-voltage terminals. Assume positive-sequence operation.