A single-phase step-down transformer is rated 13MVA,66kV11.5kV. With the 11.5kVwinding short-circuited, rated current flows when the voltage applied to the primary is 5.5kV. The power input is read as 100 kW. DetermineReq1andXeq1 in ohms referred to the high-voltage winding.

Short Answer

Expert verified

The equivalent winding resistance is 2.57Ω and equivalent leakage reactance is27.8Ω .

Step by step solution

01

Determine the formulas of apparent power, real power and equivalent impedance

Write the formula of apparent power

S1=E1I1 ……. (1)

Write the formula of power absorbed by real power

P=I12Req ……. (2)

Write the formula of equivalent impedance

Z=E1'I1 ……. (3)

Write the formula of equivalent leakage reactance

Xeq=(Zeq)2-(Req)2 ……. (4)

02

Determine the equivalent winding resistance and equivalent leakage reactance.

Determine rated current at 66 kV.

Substitute 13MVA for S1and 66 kV for E1 in equation (1).

S1=E1I113×106=66×103I1I1=196.96A

Determine the equivalent resistance.

Substitute 100 kW for Pand 196.96A for I1 in equation (2)

P=I12Req100×103=196.962ReqReq=100×103196.962Req=2.57Ω

Determine the equivalent impedance

Substitute 5.5 kV for E1' and 196.96A for I1 in equation (3)

Zeq=E1'I1=5.5×103196.96=27.92Ω

Determine the equivalent reactance

Substitute 27.92Ωfor Zeqand 2.57Ωfor Reqin equation (4)

Xeq=Zeq2-Req2=27.922-2.572=27.8Ω

Therefore, the equivalent winding resistance is 2.57Ω and equivalent leakage reactance is27.8Ω .

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with Vaia!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

For the transformer in Problem 3.10, the open-circuit test with 11.5kVapplied results in a power input of 65kW and a current of 30A . Compute the values forGcand Bmin siemens referred to the high-voltage winding. Compute the efficiency of the transformer for a load of 10MW at 0.8 p.f. lagging at rated voltage.

The units of admittance, conductance, and susceptance are siemens.

(a) True

(b) False

A bank of three single-phase transformers, each rated30MVA,38.1/3.81kV, are connected in Y–with a balanced load of three1Ω, Y-connected resistors. Choosing a base of90MVA,66kVfor the high-voltage side of the three-phase transformer, specify the base for the low-voltage side. Compute the per-unit resistance of the load on the base for the low-voltage side. Also, determine the load resistance in ohms referred to the high-voltage side and the per-unit value on the chosen base.

In either aY-or-Ytransformer, as per the American Standard notation, the negative-sequence phase shift is the reverse of the positive sequence phase shift.

(a) True

(b) False

Consider the adopted per-unit system for the transformers. Specify true or false for each of the following statements:

(a) For the entire power system of concern, the value ofSbaseis not the same.

(b) The ratio of the voltage bases on either side of a transformer is selected to be the same as the ratio of the transformer voltage ratings.

(c) Per-unit impedance remains unchanged when referred from one side

of a transformer to the other.

See all solutions

Recommended explanations on Computer Science Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.

Sign-up for free