Calculate the total resistance.
Substitute for , for , for and for into equation (1).
localid="1656745017926"
Convert the total impedance from cartesian from to polar form.
(1)
Calculate the sending end voltage with above the rated voltage.
Calculate the line current.
Substitute for and for into equation (2).
Hence the line current is .
(2)
Calculate the voltage drop across the line.
Substitute for , for and for into equation (3).
role="math" localid="1656746756778"
Hence the voltage drop across the line is .
(3)
Calculate the line-to-line load voltage.
Substitute the for and for into equation (4).
Hence the line-to-line load voltage is .
(4)
Calculate the real power delivered to the load.
Substitute for and for into equation (5).
Calculate the reactive power delivered to the load.
Substitute for and for into equation (6).
Hence the real power delivered to the load is and reactive power delivered to the load is
(5)
Calculate the power factor.
Substitute for and for into equation (7).
Hence the power factor is 0.832 lagging.
(6)
Calculate the real power line losses.
Substitute for and for into equation (8)
Calculate the reactive line losses.
Substitute for and for into equation (9)
Hence the real and reactive power line losses are 0.408 MW and 0.817 Mvar respectively.
(7)
Calculate the real power delivered to distribution substation.
Substitute 3.775MW for PLOAD and 0.408 MW for PLINELOSS into equation (10).
Calculate the reactive power delivered to distribution substation.
Substitute 2.517 Mvar for QLOAD and 0.817 Mvar for QLINELOSS into equation (11).
Calculate the complex power.
Substitute 4.183MW for PSOURCE and 3.324 Mvar for QSOURCE into equation (12).
Hence the real, reactive and apparent power are 4.183 MW , 3.324 Mvar and 5.343 MVA respectively.